47
Henrad CC FF
- Installation
76 PRESSURE RELIEF VALVE (Safety Valve) REPLACEMENT
77
CH EXPANSION VESSEL REPLACEMENT
SERVICING
SER
VICING
1. Isolate the electrical supply. Refer to Frame 54.
2. Remove pump. Refer to Frame 69.
3. Disconnect the mains electrical connection from the
bottom panel. Disengage the 2 halves of the connector.
4. Remove the boiler bottom panel.
5. Close the cocks on the CH flow and return pipework
below the boiler. Drain down. Refer to Frame 68.
6. Disconnect the discharge pipe to the pressure relief valve.
7. Undo the connection securing the valve to the boiler.
8. Replace with a new valve and restore the pipework, in
reverse order, using new sealing washer.
9. Open cocks, fit filling loop, fill, vent and pressurise to 1 bar
(or as required).
10. Restore the electrical supply and set the heating controls,
to test-fire the boiler.
11. Vent air and top up the pressure again, as required.
12. Remove the filling loop.
If the CH expansion vessel is faulty, there are 3 options:
A. If it has a punctured diaphragm, but is
otherwise leak free, then
it can be left in place and a new vessel added to the system,
external to the boiler, provided it is of adequate capacity and
pre-charge pressure.
B. If there is at least 600mm clearance above the boiler, the
expansion vessel can be changed without removing the boiler
(RH exit flues will have to be disturbed). Access to the water
connection of the expansion vessel is
either by removal of the
right hand side boiler panel (if there is 200mm RHS clearance)
or by removal of the fan and gas valve.
C. If there is insufficient headroom, the boiler will need to be
removed. In this case, access to the water connection of the
expansion vessel will be possible by removing the RH boiler
side panel.
For option B, proceed as follows:
B1. Isolate the electric, gas, and
water services.
Summary of Contents for CC 100 FF
Page 1: ......