Installation Instructions and Instructions for Use
Subject to technical modifications. – Date of Issue
September/2020
23
Installation on brickwork 60-170 mm ETICS
Installation of the anchor rod as per
approval ETA-10/0383:
Depending on the type of stone, the
injection anchor sleeve must be used!
- Drilled hole preparation
ø18 mm without sleeve
ø20 mm with sleeve (20x200)
- Drilled hole cleaning
- Fill drilled hole (anchor sleeve) with
mortar FIS V
- Slide the anchoring element into
the drilled hole
- Wait for the curing time
Installation of the Thermax as per
approval Z-21.8-1837:
- Mill open the thermal insulation
prior to injection
- Sealing of the expansion joint
Installation of the attachment:
- Tightening torque as per Z-21.8-
1837
- Sealing of the free elongated hole
parts
Legend
Brickwork
Bracket
Installation set 3; Thermax 16/170
M12
Thickness of the non-bearing layer
up to 170 mm
ETICS
Anchoring depth 200 mm = drilled
hole depth
1
2
3
4
5
6
Installation Instructions and Instructions for Use
24
Subject to technical modifications. – Date of Issue
September/2020
Installation on wood
Installation of the attachment:
- Drilled hole preparation ø9 mm
- Secure bracket with wood screw
and washer
Legend
Wood
Installation set 5; wood screw ø12x120
Bracket
Drilled hole depth 125 mm
No wind protection class can be given with installation on wood due to the
variance of the building material.
1
2
3
4
Installation Instructions and Instructions for Use
Subject to technical modifications. – Date of Issue
September/2020
25
Installation on wood 60-170 mm ETICS
Installation of the anchor rods:
- Drilled hole preparation ø14 mm
- Observe the anchoring depth and
the minimum edge distance of 100
mm!
- Drilled hole cleaning
- Lubricate threaded rod
- Screw threaded rod into the wood
Installation of the Thermax following
approval Z-21.8-1837:
- Milling open the thermal insulation
- Sealing of the expansion joint
Installation of the attachment:
- Sealing of the free elongated hole
parts
Legend
Wood
Bracket
Installation set 3; Thermax 16/170
M12
Thickness of the non-bearing layer
up to 170 mm
ETICS
Anchoring depth 140 mm = drilled
hole depth
Required wood quality is C24, P30, GL24, F40/30 or equivalent with a
ZRRGPRLVWXUHRI
2
3
4
5
6
1
Installation Instructions and Instructions for Use
26
Subject to technical modifications. – Date of Issue
September/2020
Installation on concrete ceiling face, installation set
10
Register constructional situation:
- Thickness of the concrete ceiling
- Determination of the theoretical
position of the concrete ceiling
(consider differences is in the
ground)
- Determination of the non-bearing
layer ETICS (adhesive, insulation,
plaster)
Legend
Brickwork
Concrete ceiling
ETICS
Ceiling position
Thickness of the non-bearing layer
Exclude the shape of the wooden
spacer under consideration of the
edge distances
The wooden spacers should rigidly be
seated in the insulation.
Using a "multi-cutter" tool is
recommended for cutting out the
insulation.
The two lower drilled holes of the bracket should be preferred for
installation. The third drilled hole serves for refitting potential errors (e.g.
wrong assessment of the constructional situation or position of the
concrete ceiling).
≥ 180
1
2
3
4
5
4