CODESYS‐V3 Soft PLC (WGX001 only)
PMX
A4354-2.2
HBM: public
347
18.7 Task configuration
The following task types can be selected under Main
Task:
S
Cyclic
The task is started asynchronously to the measured
values.
The interval must be at least 4 ms
, that is
the shortest possible resolution.
S
External - Measval Event
The task is started synchronously with the acquired
measured values. The calling frequency is set in the
"System Options" dialog. Default: 1,200 Hz, i.e. at a
sampling rate of 19,200 Hz, the task is started after
every 16th measured value.
S
External - SystemEvent
The task is started when a PMX system event occurs
(this event is also displayed in the device system log).
The number of the event is delivered within the task
by the library function getSystemeventNo (see chap
ter 18.10). .
The system events can be called up via the browser
with the device path http://<pmx devicename>/data/
systemevent.xml.
Where possible, only select these task types
Summary of Contents for PX401
Page 1: ...Operating Manual English PMX...
Page 104: ...Electrical connections PMX 104 A4354 2 2 HBM public PMX...
Page 141: ...Startup PMX A4354 2 2 HBM public 141 Network settings...
Page 239: ...Internal calculation channels PMX A4354 2 2 HBM public 239...
Page 241: ...Internal calculation channels PMX A4354 2 2 HBM public 241...
Page 246: ...Internal calculation channels 246 A4354 2 2 HBM public PMX...
Page 264: ...Internal calculation channels 264 A4354 2 2 HBM public PMX...
Page 272: ...Parameter sets measurement programs 272 A4354 2 2 HBM public PMX...
Page 295: ...Communication with a control system PMX A4354 2 2 HBM public 295...
Page 297: ...Communication with a control system PMX A4354 2 2 HBM public 297...
Page 300: ...Communication with a control system 300 A4354 2 2 HBM public PMX...
Page 376: ...CODESYS V3 Soft PLC WGX001 only 376 A4354 2 2 HBM public PMX...
Page 378: ...CODESYS V3 Soft PLC WGX001 only 378 A4354 2 2 HBM public PMX...
Page 381: ...CODESYS V3 Soft PLC WGX001 only PMX A4354 2 2 HBM public 381...
Page 392: ...CODESYS V3 Soft PLC WGX001 only 392 A4354 2 2 HBM public PMX Dialog Updating the PMX device...
Page 489: ...Object directory PMX A4354 2 2 HBM public 489...
Page 523: ...Diagnosis and maintenance PMX A4354 2 2 HBM public 523 Network settings...