Internal calculation channels
PMX
A4354-2.2
HBM: public
223
13.2.4.11Connection with (optional) delay
(CODESYS)
Function
output Y = input X
Purpose: Easy connection of a CODESYS channel to a
calculated channel output
The connection forwards the input signal on the output,
optionally with a delay. You can duplicate the input signal
with this function to forward it to other functions such as
filters. For PMX versions with CODESYS (WGX001), the
function is also suitable for forwarding values or signals
that have been determined to other channels or outputs.
Inputs
X
Outputs
Y
Parameters
-
Default
Input X: constant 0.0
Exception handling
If the input is marked as invalid (Invalid bit), the output are
also marked as invalid. The input value is nonetheless
output.
13.3 Example calculations
13.3.1 Generation of peak values
Before starting your configuration, make sure you have
the necessary rights to make any changes.
Click the
person symbol
in the top right corner and
choose
maintenance
or
administrator
.
Now click >
Settings
>
Calculated channels
.
Click “add function”
1
you are now able to choose one
out of many functions for every single channel. In this
example we choose “Peak value” for channel 5.
Summary of Contents for PX401
Page 1: ...Operating Manual English PMX...
Page 104: ...Electrical connections PMX 104 A4354 2 2 HBM public PMX...
Page 141: ...Startup PMX A4354 2 2 HBM public 141 Network settings...
Page 239: ...Internal calculation channels PMX A4354 2 2 HBM public 239...
Page 241: ...Internal calculation channels PMX A4354 2 2 HBM public 241...
Page 246: ...Internal calculation channels 246 A4354 2 2 HBM public PMX...
Page 264: ...Internal calculation channels 264 A4354 2 2 HBM public PMX...
Page 272: ...Parameter sets measurement programs 272 A4354 2 2 HBM public PMX...
Page 295: ...Communication with a control system PMX A4354 2 2 HBM public 295...
Page 297: ...Communication with a control system PMX A4354 2 2 HBM public 297...
Page 300: ...Communication with a control system 300 A4354 2 2 HBM public PMX...
Page 376: ...CODESYS V3 Soft PLC WGX001 only 376 A4354 2 2 HBM public PMX...
Page 378: ...CODESYS V3 Soft PLC WGX001 only 378 A4354 2 2 HBM public PMX...
Page 381: ...CODESYS V3 Soft PLC WGX001 only PMX A4354 2 2 HBM public 381...
Page 392: ...CODESYS V3 Soft PLC WGX001 only 392 A4354 2 2 HBM public PMX Dialog Updating the PMX device...
Page 489: ...Object directory PMX A4354 2 2 HBM public 489...
Page 523: ...Diagnosis and maintenance PMX A4354 2 2 HBM public 523 Network settings...