![HBK DSE Operating Manual Download Page 32](http://html1.mh-extra.com/html/hbk/dse/dse_operating-manual_2111691032.webp)
DSE
CONNECTING DSE VIA TCP/IP
30
Fig. 6.9
Adding measurement signals
u
Get the (start) addresses of the measured values from the list (Fig. 6.9). The Gross
value is 68 ... 71, and the Tare value 80 ... 83.
u
Open the Devices tab, PLC tags group and choose Add new tag table.
Fig. 6.10
Adding a new tag table
u
Add the two values as variables with the start addresses from the list. The length is
determined by the data type (REAL or F32).