Hasco H1280 Series Operating Instructions Manual Download Page 17

18   HASCO hot runner    

Setpoint 
value 

Specified  temperature  for  a  zone  in  normal  operating 
mode. 

Min:  

Max: 

Standard:  

0 °C 

600 °C 

0 °C 

Standby 
temperature 

It  is  recommended  that  use  be  made  of  the  standby 
function to protect the plastic melt and reduce energy 
costs. The standby temperature can be specified here 
as a function of the materials used. This determines the 
value  to  which  the  zones  should  cool  down.  The 
standby function is activated in the menu bar with the 

“Pause” button 

 or, alternatively, via a control input. 

Min:  

Max: 

Standard:  

0 °C 

300 °C 

150 °C 

Boost 
increase 

By  implementing  the  boost  function,  the  setpoint 
temperature for individual zones or groups is raised by 
an adjustable value for a specified period of time. This 
function can be used to heat up nozzle tips in order to 
clear  them  prior  to  start-up.  The  boost  function  is 
activated from the home view. The editor with the boost 
button can be opened by clicking on a zone. 

 

Min:  

Max: 

Standard:  

0 K 

50 K 

0 K 

Boost 
duration 

For setting the time mentioned above for which a zone 
is to be boosted. 

Min:  

Max: 

Standard:  

0 sec 

900 sec 

60 sec 

5.3.1.2 

Monitoring 

5.3.1.2.1  Temperature monitoring 

 

 

1. 

  2. 

  3. 

 

 

Setup > Monitoring > Temperature 

 
Different temperature limits can be set on the temperature monitoring page. 

Procedure:  

 

First select the zones on the left whose temperature limit is to be changed  
(see chapter Selection of zones and groups for operation)  

 

On the right side, select one of the values described below  

 

Open the box for entering the setpoint value with 

 

 

Enter the desired value in the input box  

 

Confirm with OK. 

1)   

Value 

 

Setting limits 

Limit for 
excessively 
high 
temperature 

If  the  actual  value  exceeds  the  limit  value  set 
here,  the  corresponding  zone  will  depict  a 

corresponding symbol: 

 

The LED strip will light up red and the zone will 
temporarily  turn  off  its  output.  A  potential-free 
contact  can  signal  this  alarm  to  the  outside.  If 
the actual value falls below this limit value, this 
alarm will automatically deactivate.  

Min:  

Max: 

 

Standard:  

0 °C 

600°C sensor type 

800°C sensor type 

400 °C 

Summary of Contents for H1280 Series

Page 1: ...D GB F 07 19 HK H1280 Multi zone control unit Operating instructions...

Page 2: ...m the basis for the safe handling of HASCO hot runner technology The instructions and information given here and particularly the safety rules must be followed under all circumstances The general safe...

Page 3: ...mould 11 4 2 Operating and display concept 11 4 2 1 Main switch 11 4 2 2 Status display 11 4 2 3 Operation 11 5 Start menu 12 5 1 Navigation bar 13 5 2 Selection of zones and groups for operation 14 5...

Page 4: ...4 Timer 37 5 3 3 1 5 User administration 38 5 3 3 1 6 File management 39 5 3 3 2 Communication 40 5 3 3 3 Service 40 5 4 Index of keywords 41 5 5 Switch all outputs on and off 41 5 6 Standby operation...

Page 5: ...or of this device cannot be held liable for direct and indirect damage resulting from improper handling or treatment 2 2 Information for operators and users The controllers are operated on the low vol...

Page 6: ...monitoring takes place in parallel via connected thermocouples In the event of deviations between the actual temperature recorded and the temperature set on the hot runner controller the heating curr...

Page 7: ...ng overview describes the main components of the hot runner controller 1 Touch display 2 USB connection 3 LED strip 4 Connection line 5 Main switch 6 Plug system example 7 Alarm socket 8 RS485 connect...

Page 8: ...so a control fuse on the internal wiring terminals 3 2 4 Connections In addition to the tiltable display the front of the housing also has a USB connection All the other connections are on the rear of...

Page 9: ...5 Wiring of plug systems 4 Commissioning 4 1 Electrical connection Important Before the device is connected to the supply voltage a check must first be performed to ensure that the mains electricity c...

Page 10: ...mould To connect the individual control zones to the corresponding injection mould use must be made of appropriate leads for the sensor and heating unit connection Please note it must always be ensur...

Page 11: ...tart The main settings for bringing a new mould into operation Start with saved settings Start the heating process with the saved settings Start with a recipe Load controller settings that have previo...

Page 12: ...een made this button releases all the control outputs The button must be pressed at length so as to avoid unintentional operating errors The symbol appears with a different background colour when outp...

Page 13: ...a finger over them in one go Zones can be allocated to a freely named group Zones that belong to a group display their group colour under the zone name To select an entire group of zones click on the...

Page 14: ...e Setup Operation Settings Mould specific Controller specific Groups Operating mode Setpoints Temperature Sensor fracture Residual current Output level Heating group Ramp gradient Soft start Run Setti...

Page 15: ...ozzles and manifolds to different groups In this way the grouped zones can be easily selected for simultaneous operation later on If no groups are to be defined this section can be skipped Procedure F...

Page 16: ...used for example to manually maintain operation of the control zone until a defective sensor is replaced OFF Zone inactive switched off If the sensor is connected the temperature monitoring of the cut...

Page 17: ...g on a zone Min Max Standard 0 K 50 K 0 K Boost duration For setting the time mentioned above for which a zone is to be boosted Min Max Standard 0 sec 900 sec 60 sec 5 3 1 2 Monitoring 5 3 1 2 1 Tempe...

Page 18: ...0 C 0 C Switch off temperature If the actual value of one zone exceeds the switch off temperature set here all the zones will be switched off The relevant zone will be marked with a corresponding alar...

Page 19: ...tivated If the limit value is exceeded a warning will be generated and in addition to drying out all the zones will be heated up to 100 C until the residual current falls below the limit value again T...

Page 20: ...ing The current will however continue to be displayed Min Max Standard 0 0 A 25 0 A 0 0 A Heating current tolerance The tolerance set here is the maximum permitted deviation of the present heating cur...

Page 21: ...separately and gently to a maximum of 100 C independently of a higher setpoint temperature Up to a temperature of 50 C each zone is heated with a maximum output level of 50 The output level is then sl...

Page 22: ...thermocouple types FeCuNi Type J and NiCrNi Type K are available for selection It is also possible to select No sensor In this case either no sensor is available or the sensor is not used The selecte...

Page 23: ...e zones with their process values faults and information on the operating status 5 3 2 1 1 General presentation The data is depicted in the following manner Zone status Presentation Zone active Black...

Page 24: ...rocess value Example in monitoring mode no output level is output and hence the process display for the output mode remains empty 50 The output level display in brackets means that the output level is...

Page 25: ...lue Setpoint value Deviation graphic Graphic presentation of the control deviation by means of a bar The height of the bar corresponds to the control deviation If the control deviation exceeds the tol...

Page 26: ...e 3 is inactive the outputs are deactivated The display boxes for the process values remain greyed out Zone 1 Actual C 235 Setpoint C 238 Active zone with the actual and setpoint value display Zone 1...

Page 27: ...ed on the controller establishes the optimum control parameters automatic optimisation As soon as the optimum control parameters have been found the word Optimised will disappear Zone 1 Manual Actual...

Page 28: ...entering the values First of all the zones for which a change is to be made are selected This can be done by clicking on the individual zones or by using the All selection button If groups have also b...

Page 29: ...gain 5 3 2 2 2 Events 1 2 3 Operation Diagnosis Events The events view contains a list of date and time dependent controller information In addition to all the warnings or alarms that occur user login...

Page 30: ...ing message The individual causes can be checked one after the other Within a cause it is also possible to use and to navigate back and forth between the instruction steps Warnings and alarms Symbol S...

Page 31: ...it for an excessively high temperature Setting limit Manual operation Wiring error Collective alarm Excessively low temperature The current temperature is below the limit for an excessively low temper...

Page 32: ...process values for actual value setpoint value and output level on a curve diagram The curve is shown in the window with a black background On the right of the screen are the arrow keys that can be u...

Page 33: ...dly the heating signal fed to the heating units 5 3 2 4 1 Control dynamics Value Description Automatic optimisation The automatic control optimisation determines the P I and D components of the contro...

Page 34: ...heating output is switched on and off at full voltage in a specific ratio The ratio of the time switched on to the time switched off is determined by the output level that is calculated by the control...

Page 35: ...the button has been pressed the dialog will open to select the recipe file First of all the directory should be selected local or possibly a USB stick plugged into the front of the controller Then th...

Page 36: ...esponding value for the year month day hour or minute 2 Pressing the arrow key increases reduces the value in the box highlighted in colour 3 The changes are adopted by pressing the button 5 3 3 1 4 T...

Page 37: ...ll be highlighted in colour To accept the new user level it is necessary to press the confirmation button The user will then be prompted to enter the password for this or the next highest level Clicki...

Page 38: ...er level The contact data for support can be found in the Service menu option Settings Service Support 5 3 3 1 6 File management 1 2 3 Settings Device File management Under file management it is possi...

Page 39: ...cation 1 2 3 Settings Device Communication Communication contains the parameters of the Ethernet interface which are required for a data exchange with the controller via the FE3 protocol 5 3 3 3 Servi...

Page 40: ...ts are retained If Reset to factory setting is selected all the parameters will be reset to their default values and all files on the device will be deleted This requires the user level Administration...

Page 41: ...tiate the temperature reduction mode in which the temperature of all the zones is reduced to the specified standby temperature This function affects all the active zones Standby is displayed in the zo...

Page 42: ...ble to NiCr Ni TYPE K 0 700 Cold junction compensation Integrated Resolution 0 1 K Accuracy 1K Load outputs Bistable electrically insulated per zone 1x heating 230V AC switching Control time phase ang...

Page 43: ...44 HASCO hot runner RS485 D SUB 9 pole USB USB 3 0 Standard 7 Dimensions 7 1 12 zone controller 7 2 24 zone controller...

Page 44: ...Bedienungsanleitung H1280 HASCO hot runner 45 7 3 36 zone controller...

Page 45: ...x 8 1 Terminal bridges for the star delta supply 8 1 1 Terminal bridges in star supply network status as delivered Figure 14 Star supply network 8 1 2 Terminal bridges in triangle supply network Figur...

Page 46: ...nt alarm socket Table 1 Alarm socket Function 1 3 Collective warning Opener 4 5 Collective alarm Opener 2 6 Unused contact Opener 8 3 Pin assignment digital input Table 2 Digital input Function 1 3 No...

Page 47: ...5 36 46 File management 47 Groups 16 18 21 Heating 24 Heating current 24 Heating signal 41 Home screen 14 15 Home view 28 I component 40 Index of keywords 50 Internal bus error 38 Internal setpoint va...

Page 48: ...e in a heating group 25 Service 48 Setpoint values 20 Settings 43 Setup 18 Soft start 25 Standby 20 Star supply network 55 Star delta supply 55 Start menu 14 Structure 8 Switch off temperature 37 Syst...

Page 49: ...HasencleverGmbH Co KG Postfach 1720 D 58467 L denscheid Tel 49 0 2351 957 0 Fax 49 0 2351 957 237 info hasco com www hasco com Subject to technical modifications Please always check all the data again...

Page 50: ...Built to run www hasco com...

Reviews: