18 HASCO hot runner
Setpoint
value
Specified temperature for a zone in normal operating
mode.
Min:
Max:
Standard:
0 °C
600 °C
0 °C
Standby
temperature
It is recommended that use be made of the standby
function to protect the plastic melt and reduce energy
costs. The standby temperature can be specified here
as a function of the materials used. This determines the
value to which the zones should cool down. The
standby function is activated in the menu bar with the
“Pause” button
or, alternatively, via a control input.
Min:
Max:
Standard:
0 °C
300 °C
150 °C
Boost
increase
By implementing the boost function, the setpoint
temperature for individual zones or groups is raised by
an adjustable value for a specified period of time. This
function can be used to heat up nozzle tips in order to
clear them prior to start-up. The boost function is
activated from the home view. The editor with the boost
button can be opened by clicking on a zone.
Min:
Max:
Standard:
0 K
50 K
0 K
Boost
duration
For setting the time mentioned above for which a zone
is to be boosted.
Min:
Max:
Standard:
0 sec
900 sec
60 sec
5.3.1.2
Monitoring
5.3.1.2.1 Temperature monitoring
1.
2.
3.
Setup > Monitoring > Temperature
Different temperature limits can be set on the temperature monitoring page.
Procedure:
First select the zones on the left whose temperature limit is to be changed
(see chapter Selection of zones and groups for operation)
On the right side, select one of the values described below
Open the box for entering the setpoint value with
Enter the desired value in the input box
Confirm with OK.
1)
Value
Setting limits
Limit for
excessively
high
temperature
If the actual value exceeds the limit value set
here, the corresponding zone will depict a
corresponding symbol:
The LED strip will light up red and the zone will
temporarily turn off its output. A potential-free
contact can signal this alarm to the outside. If
the actual value falls below this limit value, this
alarm will automatically deactivate.
Min:
Max:
Standard:
0 °C
600°C sensor type
L
800°C sensor type
K
400 °C