Manual
HM1016ER1
Technical Specification
Harsen
®
Page 54/54
10.7 Charge failure input:
Range
0 to 35Vdc
Accuracy
1%
Max output current
@12V 120mA, @24V 240mA
10.8 Analog Inputs:
Number
2
Sensor type
resistance
Resolution
10 bits
Range
0 to 1K
Ω
Accuracy
2% When full scale, except for sensor error
10.9 Magnetic pickup:
Voltage range
1 to 70V
Max. frequency
10000Hz
Fly wheel teeth
5 to 300
10.10 Ambient parameters:
Operating ambient temperature
Standards
-20 to 70
℃
IEC60068-2-1 and IEC60068-2-2
Storage ambient temperature
Standards
-30 to 80
℃
IEC60068-2-1 and IEC60068-2-2
Humidity
Standards
60
℃
, 95%RH, 48 hours
IEC60068-2-30
Electro Magnetic compatibility (EMC)
Standards
EN 61000-6-4 and EN 61000-6-2
Vibration
Standards
EN 60068-2-6
Shock
Standards
EN 60068-2-27
Electrical safety
Standards
EN 60950-1
Degrees of protection
Standards
IP65 (front) IP20 (back)
BS EN 60529