7.4 Configurable Inputs and Outputs:
NO.
Items
Preset
Value Range
4.1
D-Input 1
5
1 to 20 / 0 not used
4.2
D-Input 2
6
1 to 20 / 0 not used
4.3
D-Input 3
7
1 to 20 / 0 not used
4.4
D-Input 4
9
1 to 20 / 0 not used
4.5
D-Input 5
11
1 to 20 / 0 not used
4.6
D-Input 1 delay
0s
0 to 60s
4.7
D-Input 2 delay
0s
0 to 60s
4.8
D-Input 3 delay
0s
0 to 60s
4.9
D-Input 4 delay
0s
0 to 60s
4.10
D-Input 5 delay
0s
0 to 60s
4.11
User relay 1
20
1 to 80 / 0 not used
4.12
User relay 2
19
1 to 80 / 0 not used
4.13
User relay 3
2
1 to 80 / 0 not used
4.14
User relay 4
3
1 to 80 / 0 not used
Menu descriptions:
D-Input*:
There are 5 configurable digital inputs.
Optional items as following:
Code
Optional Functions
Note
0
not used
1
Pre-alarm (warning)
Low level is active. When it is active, pre-alarm LED
illuminates and buzzer sounds.
2
Alarm
Low level is active. When it is active, generator stops,
shutdown alarm LED illuminates and buzzer sounds.
3
Pre-alarm 1
Low level is active. When it is active after safety-on
delay, pre-alarm LED illuminates and buzzer sounds.
4
Alarm1
Low level is active. When it is active after safety-on
delay, generator stops, shutdown alarm LED illuminates
and buzzer sounds.
5
LOP switch
low level is active
6
HET switch
low level is active
7
Emergency stop
low level is active
8
Emergency stop
high level is active (N.O. is active.)
9
Remote start signal
low level is active
10
Mains Aux. Switch closed
low level is active
11
Gen Aux. Switch closed
low level is active
12
Low fuel level switch
low level is active
13
Lamp test
low level is active
14
Reserved
15
Reserved
16
Air flap Aux. switch close
low level is active
17
Preheat
Low level is active. Used for preheat mode 4, as the
condition of preheat relay output is energised or not.
18
Crisis mode
Low level is active. In crisis mode, all shutdown alarms
are changed to pre-alarm (warning), it means the Genset
would not be shutdown when shutdown alarm occurs.