Parameters Setting
Harsen
®
Page 33/54
Cool down time:
The time permit for running without load before engine stop.
It is necessary to set cool down time, it can make the engine stop at a lower temperature after a long
time running with load.
Stop delay:
The maximum time permit for the engine stop.
After the fuel relay output is de-energised (fuel relay output is energised for N.O. type fuel valve), fail
to stop delay timer begins, when it time’s out if controller detects generator’s voltage exceeds crank
cutout voltage, or the speed exceeds crank cutout speed, or LOP switch is open, or oil pressure
exceeds crank cutout oil pressure, then stop failure occurs.
If the fuel valve is N.O. type, the fuel relay output is de-energised after Stop delay has expired.
Under SP preALM:
Used to configure the under speed pre-alarm value for the engine.
When parameter is set as “0”, this function is inactive.
Under SP Alarm:
Used to configure the under speed alarm value for the engine.
When parameter is set as “0”, this function is inactive.
Over SP preALM:
Used to configure the over speed pre-alarm value for the engine.
When parameter is set as “9999”, this function is inactive.
Over SP Alarm:
Used to configure the over speed alarm value for the engine.
When parameter is set as “9999”, this function is inactive.
Oil-P low preALM:
Used to configure the low oil pressure pre-alarm for the engine.
The signal is derived form LOP sensor, this function would be inactive if do not use LOP sensor.
This function is active after safety-on delay.
When parameter is set as “0.0”, this function is inactive.
Oil-P low Alarm:
Used to configure the under oil pressure alarm value for the engine.
The signal is derived form LOP sensor, this function would be inactive if do not use LOP sensor.
This function is active after safety-on delay.
When parameter is set as “0.0”, this function is inactive.
Coolant preALM:
Used to configure the high engine temperature pre-alarm value for the engine.
The signal is derived form HET sensor, this function would be inactive if do not use HET sensor.
When parameter is set as “9999”, this function is inactive.