Manual
HM1016ER1
Parameters Setting
Harsen
®
Page 27/54
7.3 ENGINE:
NO.
Items
Preset
Value Range
3.1
Rated speed
1500RPM
99 to 9999 RPM
3.2
MPU input
0
0 NO / 1 YES
3.3
Fly wheel teeth
120
5 to 300
3.4
Set pickup now
3.5
Pair of Poles
2
1 to 4
3.6
Fuel mode
0
0 N.C. / 1 N.O.
3.7
T-sensor type
3
1 to 15 / 0 not used
3.8
P-sensor type
4
1 to 15 / 0 not used
3.9
Start delay
10s
0 to 300s
3.10
Crank attempt
3 times
1 to 10 times
3.11
Crank time
5s
1 to 30s
3.12
Crank time add
0
1 to 30s / 0 not used
3.13
Crank rest
10s
1 to 300s
3.14
Crank cutout RPM
300RPM
1 to 9999 RPM
3.15
Crank cutout volt
85%
1 to 100% / 999 not used
3.16
Crank cutout ALT-V
99.9
1.0 to 40.0V / 99.9 not used
3.17
Crank cutout Oil-P
1.0Bar
0.1 to 150.0 Bar / 999.9 not used
3.18
Cutout P-delay
0
1 to 60s / 0 not used
3.19
Idle time
0
1 to 9999s / 0 not used
3.20
Pre-heat mode
1
1 to 4
3.21
Pre-heat time
3s
1 to 9999s / 0 not used
3.22
Safety-on delay
10s
0 to 600s
3.23
Cool down mode
0
0 full speed / 1 idle
3.24
Cool down time
300s
0 to 600s
3.25
Stop delay
20s
0 to 60s
3.26
Under SP preALM
1440RPM
1 to 9999 RPM / 0 not used
3.27
Under SP Alarm
0
1 to 9999 RPM / 0 not used
3.28
Over SP preALM
1600RPM
1 to 9999 RPM / 9999 not used
3.29
Over SP Alarm
1710RPM
1 to 9999 RPM / 9999 not used
3.30
Oil-P low preALM
1.4Bar
0 to 150.0 Bar / 0.0 not used
3.31
Oil-P low Alarm
1.1Bar
0 to 150.0 Bar / 0.0 not used
3.32
Coolant preALM
92
℃
50 to 320
℃
/ 9999 not used
3.33
Coolant Alarm
100
℃
50 to 320
℃
/ 9999 not used
3.34
Batt. Undervolt
8.0V
1.0 to 40.0V / 0 not used
3.35
Batt. overvolt
28.0V
1.0 to 40.0V / 99.9 not used
3.36
Alt. low preALM
8.0V
1.0 to 40.0V / 0 not used
3.37
EX. Crank permit
0
0 NO / 1 YES
Menu descriptions:
Rated speed:
Used to configure the Genset rated speed.
A reference value for speed control.