51
V01 05/2016 1003370
Table 51.1 YukonDrive® climatic conditions
Table 51.2 YukonDrive® mechanical conditions
Climatic conditions
YukonDrive®
in transit
as per EN 61800-2, IEC 60721-3-2 class 2K3
1)
Temperature
-25 °C to +70 °C
Relative humidity
95 % at max. +55 °C
in storage
as per EN 61800-2, IEC 60721-3-1 class 1K3 and 1K4
2)
Temperature
-25 °C to +55 °C
Relative humidity
5 to 95 %
in operation
as per EN 61800-2, IEC 60721-3-3 class 3K3
3)
Temperature
-10 °C bis +40 °C
Relative humidity
5 to 85 % without condensation
1)
The absolute humidity is limited to max. 60 g/m³. This means, at 70 °C for example, that the relative humidity may only be max. 40 %.
2)
The absolute humidity is limited to max. 29 g/m³. So the maximum values for temperature and relative air humidity stipulated in the
table must not occur simultaneously.
3)
The absolute humidity is limited to max. 25 g/m³. That means that the maximum values for temperature and relative air humidity
stipulated in the table must not occur simultaneously.
Mechanical conditions
YukonDrive®
Vibration limit in transit
as per EN 61800-2, IEC 60721-3-2 class 2M1)
1)
Frequency [Hz]
Amplitude [mm]
Acceleration [m/s²]
2 ≤ f < 9
3.5
Not applicable
9 ≤ f < 200
Not applicable
10
200 ≤ f < 500
Not applicable
15
Shock limit in transit
as per EN 61800-2, IEC 60721-2-2 class 2M1
Drop height of packed device max. 0.25 m
Vibration limits of the
system
1)
as per EN 61800-2, IEC 60721-3-3 class 3M1
3)
Frequency [Hz]
Amplitude [mm]
Acceleration [m/s²]
2 ≤ f < 9
0.3
Not applicable
9 ≤ f < 200
Not applicable
1
1)
Note: The devices are only designed for stationary use.
Attention!
• No permanent vibration!
The drive controllers must not be installed in areas where they would be permanently exposed to vibration.
• Switch cabinet min. IP54 for STO!
According to EN ISO 13849-2, when using the STO (Safe Torque OFF) safety function the switch cabinet must have
IP54 protection or higher.
• Observe cooling conditions!
Forced cooling by external air flow is necessary. Air must be able to flow unhindered through the device (air flow at
least 1.2 m/s). If a temperature cut-out occurs, the cooling conditions must be improved.