Designation
Technical data
-1022
-1032
-1042
Output. motor side
1)
Voltage
3-phase U
Netz
Effective continuous current (l
N
)
2)
2 A
3.5 A
6.5 A
Peak current (A
eff
)
6 A
10.5 A
19.5 A
Rotating field frequency
0 ... 400 Hz
Switching frequency of power stage
4. 8. 16 kHz
Input. mains side
Mains voltage
(3 x 400 V AC / 3 x 460 V AC / 3 x 480 V AC) ±10 %
Device connected load
1)
(with line reactor)
1.5 kVA
2.7 kVA
5.0 kVA
Current
1)
(with line reactor)
2.2 A
3.9 A
7.2 A
Asymmetry of mains voltage
±3 % max.
Frequency
50/60 Hz ±10 %
Power loss at I
N
1)
42 W
80 W
150 W
Braking chopper power electronics
Peak braking power with int. braking resistor
2400 W in 7500 Ω
(PTC)
4)
1 kW in 420 Ω
5))
4.7 kW in 90 Ω
5)
Minimum ohmic resistance of an externally installed
braking resistor
230 Ω
180 Ω
3)
72 Ω
3)
1)
Values referred to mains voltage 400 V AC and switching frequency 8 kHz.
2)
For rated current refer to table 33!
3)
Connection of ext. braking resistor not permitted to devices with int.braking resistor!
4)
Braking resistor always integrated. Connection of an external resistor is permissible
5)
Option
Table 50.1 technical data YukonDrive® -1022/ -1032/ -1042
Note:
For more information on the braking chopper switch-on threshold also refer to section 3.14 as from page 34.
Table 50.2 YukonDrive® climatic conditions
A.3 Ambient conditions
Ambient conditions
YukonDrive®
Protection
IP20 except terminals (IP00)
Accident prevention regulations
according to local regulations (in Germany e.g. BGV A3)
Mounting height
to 1000 m above MSL, over 1000 m above MSL with power reduction
(1 % per 100 m, max. 2000 m above MSL)
Pollution severity
2
Type of installation
Built-in unit, only for vertical installation in a switch cabinet with min. IP4x pro-
tection, when using STO safety function min. IP54