28
1003370 05/2016 V01
3.9 Specification of Ethernet port
The service and diagnostic interface X9 is executed as a TCP/IP Ethernet port. It is suitable for connection of a PC for
commissioning, service and diagnosis and for programming of the drive controller. The following software can com-
municate via the Ethernet port with the drive controller:
• Harmonic Drive AG DriveManager 5 for commissioning, service and diagnosis of the YukonDrive®
• CoDeSys 3.x programming system for programming of the YukonDrive® in the languages of IEC 61131-3.
This requires a drive controller licence.
Specification of interface:
• Transfer rate 10/100 MBits/s BASE
• Line protocol IEEE802.3 compliant
• Connection via standard commercially available crosslink cable, CAT 5
3.10 Option 1
Depending on the YukonDrive® variant, option 1 is factory-configured with various options. Field bus options such as
EtherCAT or SERCOS are available.
You will find all available options in the Harmonic Drive® catalogue.
The Operating Manuals for the respective options provide detailed information on commissioning.
3.11 Option 2
Option 2 can be factory-configured with various technology options. Additional or special encoders can be evaluated
with it for example. You will find all available options in the Harmonic Drive® catalogue. The Operating Manuals for the
respective options provide detailed information on commissioning.
Note:
For the connection of the motor feedback system of the FHA-C-Mini series, Option 2 = B (TTL encoder with commuta-
tion signals) should be used!
Table 28.1 Specification of terminal connections X13
3.8.2 Connection of motor brake X13
Connector X13 (BG2 to BG4) is intended for connection of a motor brake.
Des.
Term.
Connection
Specification
OSD03
GND
GND
V+
X13/2
X13/1
X13/3
X13/4
Short-circuit proof
External control 24 V DC
(I
IN
= 2,1 A) required via X13/3
(GND) and X13/4 (V+)
U
BR
= U
V
-∆U` (∆U` typically approx. 1,4 V)
To actuate a motor holding brake up to I
BR
= 2,0 A max. (for brakes
with higher current requirements a relay must be inter posed).
Overcurrent causes cyclic shutdown
Also usable as configurable digital output
Interruptible cable break monitor <200 mA typically in condi-
tion “1”
Motor
3
GND
OSD03
1
2
~
X13
Front
Brake (+)
Brake (-)
V+
GND
3
4
24V DC
supply
for brake