Maximum flue resistive length = 30m.
3f
A flue system can be built up from the components
detailed in the table, but the total flue resistance must
not exceed the maximum stated.
flue will be routed vertically alongside the outside wall to above
the roofline. Special seals are required to prevent rainwater
penetrating the pipe joints.
For installation details refer to the flue kit instructions.
This kit is suitable for open flue application in accordance with BS5440
where a room sealed flue installation is impractical. The kit comprises of
a flue adaptor from the appliance to the chimney, a flexible plastic flue
liner with connection parts and chimney terminal (see Figure 3f). Where
an open flue system is used, then an air vent must be provided in the
same room or internal space as the flue duct air inlet, see section 3.4.
For installation details refer to the flue kit instructions.
(B23) – PART NO. 956082
2.6
KIT E CHIMNEY FLUE LINER KIT
It has to be noted that the flue duct is under pressure when the
appliance is in operation and the duct can leak poisonous carbon
monoxide if the duct components are not correctly assembled. It is
not
recommended to route the flue duct through living space areas, i.e.
bed rooms, living rooms etc.
For installation details refer to the instructions provided with the twin
flued kit.
For C53 flue systems the terminal for the supply of combustion air and
for the evacuation of combustion products shall not be installed on
opposite walls of the building.
Maximum flue resistance permitted for a twin flued
system = 52 Pa
Minimum flue resistance permitted for a twin flued
system = 23.5 Pa
Flue Component
Flue Resistance (Pa) Part Number
Twin Flue Adaptor (required)
9.5
-
Air Inlet Terminal (required)
3
-
Chimney Terminal (required)
0.5
-
80 mm dia straight duct 1 metre
1
956101
80 mm dia straight duct 2 metre
2
956102
90° Elbow (80/80)
8
956100
45° Elbow (80/80)
4
956099
3g
A flue system can be built up from the components
detailed in the table, but the total flue resistance must
not exceed the maximum stated.
PART NO. 956080
2.7
KIT F: TWIN FLUE SYSTEM (C53) –
This flue system kit is designed for installations where the air intake
position is different than the flue duct exit point. The kit comprises of a
twin adaptor from which the air intake is taken from the adjacent
outside wall (see example Figure 3g) and the flue duct is routed
vertically through the roof.
Summary of Contents for Eden CBX
Page 13: ...4b Domestic Hot Water Mode CBX 4c Central Heating Mode SBX 11...
Page 28: ...26 24 CBX SBX...
Page 31: ...INTERNAL WIRING DIAGRAMS 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM 29 29...
Page 44: ...42 54 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24...
Page 45: ......
Page 46: ......