App2-2
Appendix 2 n : 1 Connection (Multi-link 2)
•
This multi-link connection is available with almost all the PLC models that support 1 : 1 connection
(refer to the “Appendix”).
(The connection between the master station and the PLC is the same as the one for 1 : 1
connection.)
•
Use the RS-485 2-wire connection between stations of the V7 series. Please use Hakko
Electronics’ multi-link 2 master cable (V6-MLT) for connection between the master station (local
port 1) and the slave station (local port 2).
•
In the following cases, multi-link 2 connection is not available.
1.
A communication interface unit (example: OPCN-1, CC-LINK, Ethernet, etc) is used.
2.
The V6 series (master or slave station) is used for the temperature control network or
PLC2Way function.
•
The V7 and V6 series can be used together. The V6 series can be the master station.
(However, when V606/V606i is the master station, the slave station must be V606/V606i. Also,
depending on the hardware version of the V6 series, multi-link 2 connection may not be supported.
Refer to the V6 Hardware Specifications.)
Wiring
Connection
For V7 Series:
(a)
Connection between PLC
↔
V7 master station
The communication parameter setting and connecting method are the same as those for 1 : 1
connection.
(Refer to “Chapter 2” to “Chapter 33.”)
(b)(c)
Connection between V7 series master station
↔
V7 slave station
The connecting port for the V7 series master station depends on the selection for [Multi-Link]
(either [Modular Jack 1] or [Modular Jack 2]) on the V-SFT editor. Selection of [Modular Jack
2] is recommended. ([Editor Port] is set as default for [Modular Jack 1].)
The connecting port of the V7 series slave station should be CN1. It is recommended that
CN1 be equipped with a terminal converter “TC485” (set to 2-wire connection).
The multi-link 2 master cable (b) (V6-MLT) is 3 m long.
If the distance (c) between the V7 series master station and the V7 series slave station is
longer than 3 m, use a terminal block and connect the cables.
(d)(e)
Connection between V7 series slave station
↔
V7 slave station
Use the RS-485 2-wire connection.
It is recommended that CN1 be equipped with a terminal converter “TC485” (set to 2-wire
connection).
(b)(c)(d)(e) The maximum length between V7 series should be 500 m.
* To avoid line-noise problems, connect one terminal only so that the shielded frame ground of each
cable will not be connected between the V7 series.
The shielded frame ground of V6-MLT must be connected to the V7 series master station.
PLC
CN1
CN1
MJ2
(a)
(b)
(c)
(d)
(e)
CN1
CN1
Communications between V7 series: RS-485 (2-wire), maximum length = 500 m
V7 master station
(= Local Port 1)
V7 slave station
(= Local Port 2)
V7 slave station
(= Local Port 3)
V7 slave station
(= Local Port 4)
Terminal
block
Summary of Contents for V Series
Page 1: ...V Series...
Page 35: ...2 10 2 Allen Bradley PLC Please use this page freely...
Page 41: ...3 6 3 Automationdirect PLC Please use this page freely...
Page 49: ...6 4 6 FANUC PLC Please use this page freely...
Page 53: ...7 4 7 FATEK AUTOMATION PLC Please use this page freely...
Page 79: ...12 8 12 KEYENCE PLC Please use this page freely...
Page 95: ...14 8 14 LG PLC Please use this page freely...
Page 119: ...16 20 16 MITSUBISHI ELECTRIC PLC Please use this page freely...
Page 135: ...20 4 20 SAIA PLC Please use this page freely...
Page 155: ...24 12 24 Siemens PLC Please use this page freely...
Page 163: ...27 4 27 TOSHIBA PLC Please use this page freely...
Page 169: ...29 4 29 Toyoda Machine Works PLC Please use this page freely...
Page 185: ...33 6 33 Yokogawa Electric PLC Please use this page freely...
Page 215: ...App2 8 Appendix 2 n 1 Connection Multi link 2 Please use this page freely...
Page 221: ...App3 6 Appendix 3 n 1 Connection Multi link Please use this page freely...
Page 225: ...App4 4 Appendix 4 1 n Connection Multi drop Please use this page freely...
Page 317: ...App6 48 Appendix 6 Universal Serial Communications Please use this page freely...