Details
•
$s729
An execution result of macro command TEMP_READ, TEMP_WRITE, or TEMP_CTL is stored at
this address.
- [0]:
A command has been executed successfully.
- [Other than “0”]:
A command execution has resulted in an error.
•
$s730-761
The following status code for the PLC connected at the MJ port is stored.
Errors other than the above are stored as shown below.
Solution
1.
Check the parameter setting of the PLC connected at the MJ port and the setting in the [Temp.
CTRL/PLC2Way Comm. Setting] dialog.
2.
Check the cable connection.
3.
Data may be disrupted because of noise. Fix noise.
* If you still cannot solve the error even after following the suggestions above, contact your local
distributor.
Code
Contents
0000H
Normal
FFFFH
Timeout
8001H
Check code error
8002H
Data error
800BH
Error code received from the PLC connected at the MJ port
Buffer-full error
Parity error
Overrun error
Framing error
Break detection
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
0
0
MSB
LSB
Error
0: Bits 0 to 14 are all “0.”
1: Any bit 0 to 14 is not “0.”
Error
Details
Solution
Timeout
Although a request to send is given to the PLC connected
at the MJ port, no answer is returned within the specified
time.
Check 1, 2, 3 described below.
Check code error
The check code in the PLC connected at the MJ port
response was not correct.
Check 1, 3 described below.
Data error
The code of the received data is invalid.
Check 1, 2, 3 described below.
Error code received
An error occurs at the PLC connected at the MJ port.
Refer to the instruction manual for the PLC.
Buffer full
The V7 buffer is full.
Contact your local distributor.
Parity
An error occurred in parity check.
Check 2, 3 described below.
Overrun
After one character is received, the next character is
received before internal processing is completed.
Check 1, 3 described below.
Framing
Although the stop bit must be [1], it is detected as [0].
Check 1, 2, 3 described below.
Break detection
SD (TXD) of the PLC connected at the MJ port remains at
the low level.
Examine the connection between SD (TXD)
of the PLC connected at the MJ port and RD
(RXD) of the V7 series.
Summary of Contents for V Series
Page 1: ...V Series...
Page 35: ...2 10 2 Allen Bradley PLC Please use this page freely...
Page 41: ...3 6 3 Automationdirect PLC Please use this page freely...
Page 49: ...6 4 6 FANUC PLC Please use this page freely...
Page 53: ...7 4 7 FATEK AUTOMATION PLC Please use this page freely...
Page 79: ...12 8 12 KEYENCE PLC Please use this page freely...
Page 95: ...14 8 14 LG PLC Please use this page freely...
Page 119: ...16 20 16 MITSUBISHI ELECTRIC PLC Please use this page freely...
Page 135: ...20 4 20 SAIA PLC Please use this page freely...
Page 155: ...24 12 24 Siemens PLC Please use this page freely...
Page 163: ...27 4 27 TOSHIBA PLC Please use this page freely...
Page 169: ...29 4 29 Toyoda Machine Works PLC Please use this page freely...
Page 185: ...33 6 33 Yokogawa Electric PLC Please use this page freely...
Page 215: ...App2 8 Appendix 2 n 1 Connection Multi link 2 Please use this page freely...
Page 221: ...App3 6 Appendix 3 n 1 Connection Multi link Please use this page freely...
Page 225: ...App4 4 Appendix 4 1 n Connection Multi drop Please use this page freely...
Page 317: ...App6 48 Appendix 6 Universal Serial Communications Please use this page freely...