16. MITSUBISHI ELECTRIC PLC
16-17
Settings and Communications
1.
PLC type setting
Select [PLC Type] from the [System Setting] menu. Select a type adapted to the ladder transfer
function in the [Select PLC Type] dialog.
2.
PLC programming software port setting
Select [Modular Jack] from the [System Setting] menu.
Select [Ladder Tool] for [Modular Jack 1] or [Modular Jack 2] in the [Modular Jack] dialog.
Communications with V-SFT Editor (for Screen Data Transfer)
•
With [Ladder Tool] selected for [Modular Jack 2], MJ1 will be [Editor Port] when the Main Menu
screen is displayed on the V7 series, and communications with the V-SFT editor become possible.
•
With [Ladder Tool] selected for [Modular Jack 1], even when the Main Menu screen is displayed on
the V7 series, communications with the V-SFT editor are not avaliable. There are two methods for
enabling communications with the V-SFT editor.
* With the V609E, employ the method for automatically enabling communications with V-SFT.
At this time, check the system program version and update it if the version is old before
transferring the screen data.
- Enabling V-SFT communications automatically (adapted to V-SFT editor version 2.0.9.0 or
later, V7 system program version 1.080 or later, and V6 system program version 1.570 or
later)
To enable communications with the V-SFT editor automatically when the Main Menu
screen is displayed, make the following settings on V-SFT.
From the [System Setting] menu, select [Unit Setting], and open the [Environment Setting]
tab window. In the window, check [Ladder Communication Is Not Used in Local Mode].
* On-line editing between the V-SFT editor and the V7 series is not possible. If attempted,
communications between the PLC programming software and the PLC will not be performed
correctly.
Summary of Contents for V Series
Page 1: ...V Series...
Page 35: ...2 10 2 Allen Bradley PLC Please use this page freely...
Page 41: ...3 6 3 Automationdirect PLC Please use this page freely...
Page 49: ...6 4 6 FANUC PLC Please use this page freely...
Page 53: ...7 4 7 FATEK AUTOMATION PLC Please use this page freely...
Page 79: ...12 8 12 KEYENCE PLC Please use this page freely...
Page 95: ...14 8 14 LG PLC Please use this page freely...
Page 119: ...16 20 16 MITSUBISHI ELECTRIC PLC Please use this page freely...
Page 135: ...20 4 20 SAIA PLC Please use this page freely...
Page 155: ...24 12 24 Siemens PLC Please use this page freely...
Page 163: ...27 4 27 TOSHIBA PLC Please use this page freely...
Page 169: ...29 4 29 Toyoda Machine Works PLC Please use this page freely...
Page 185: ...33 6 33 Yokogawa Electric PLC Please use this page freely...
Page 215: ...App2 8 Appendix 2 n 1 Connection Multi link 2 Please use this page freely...
Page 221: ...App3 6 Appendix 3 n 1 Connection Multi link Please use this page freely...
Page 225: ...App4 4 Appendix 4 1 n Connection Multi drop Please use this page freely...
Page 317: ...App6 48 Appendix 6 Universal Serial Communications Please use this page freely...