![background image](http://html1.mh-extra.com/html/hakko-electronics/v-series/v-series_connection-manual_3303640233.webp)
App5-8
Appendix 5 Ethernet
•
10BASE2
The following devices are required for 10BASE2 connection:
- Coaxial cable for 10BASE2
- AUI cable
- T-type adaptor
- Terminator for 10BASE2
- Transceiver
- Power supply for the transceiver: 12 VDC
•
Transceiver
Use the transceiver equipped with the SQE TEST function.
(SQE TEST: Signal Quality Error Test)
Recommended transceiver
* The I/F unit may be broken if the AUI connector is subject to strong force. Use the AUI cable
when connecting the transceiver.
* When the power lamp of the transceiver is not turned on, check the wiring of 12 VDC power
supply, then replace the fuse (refer to page App5-4) of the I/F unit CU-03-2.
For the replacement procedure, refer to the manual “CU-03-2 OPERATING INSTRUCTIONS,”
attached to CU-03-2.
Manufacturer
Type
Allied Telesis
CentreCOM 107
CU-03
V7
PLC
PLC
Maximum segments:
5
Maximum network distance: 925 m
Maximum network nodes:
100
Ethernet
unit
1 segment (max. 185 m, max. 30 nodes)
AUI cable
(max 50 m)
Transceiver
*2
Terminator
T-type
Node
Node
*1
Repeater
Minimum node
interval
0.5 m
To extend the segment distance or
increase the number of nodes, use
repeaters.
*1
The unit may have a built-in transceiver.
Refer to the instruction manual for the unit.
*2
12 V power supply is required for each transceiver.
Ethernet
unit
*1
Summary of Contents for V Series
Page 1: ...V Series...
Page 35: ...2 10 2 Allen Bradley PLC Please use this page freely...
Page 41: ...3 6 3 Automationdirect PLC Please use this page freely...
Page 49: ...6 4 6 FANUC PLC Please use this page freely...
Page 53: ...7 4 7 FATEK AUTOMATION PLC Please use this page freely...
Page 79: ...12 8 12 KEYENCE PLC Please use this page freely...
Page 95: ...14 8 14 LG PLC Please use this page freely...
Page 119: ...16 20 16 MITSUBISHI ELECTRIC PLC Please use this page freely...
Page 135: ...20 4 20 SAIA PLC Please use this page freely...
Page 155: ...24 12 24 Siemens PLC Please use this page freely...
Page 163: ...27 4 27 TOSHIBA PLC Please use this page freely...
Page 169: ...29 4 29 Toyoda Machine Works PLC Please use this page freely...
Page 185: ...33 6 33 Yokogawa Electric PLC Please use this page freely...
Page 215: ...App2 8 Appendix 2 n 1 Connection Multi link 2 Please use this page freely...
Page 221: ...App3 6 Appendix 3 n 1 Connection Multi link Please use this page freely...
Page 225: ...App4 4 Appendix 4 1 n Connection Multi drop Please use this page freely...
Page 317: ...App6 48 Appendix 6 Universal Serial Communications Please use this page freely...