Appendix 5 Ethernet
App5-43
•
System memory: $s518
No.
Contents
Solution
0
Normal
200
Failed in send request
Check cable connection and network table setting of
the target station.
201
Send error
Check that the setting on the target station is
consistent with the network table setting.
202
Internal port error
The communication unit is in the older version or is
faulty.
204
TCP connection over
The number of connections reaches the maximum,
and no more connection is possible.
Check the communication lines.
205
TCP connection error
Connection cannot be established.
Check the communication lines, or turn the power off
and on.
206
TCP connection end error
TCP communication disconnection has failed.
Check that the communication partner with the V7
series is present on the line.
207
TCP send error
TCP communication has failed.
Check the communication lines.
350
Send buffer full
The line is busy. Consult the network administrator
of your company.
The communication unit is in the older version or is
faulty.
351
IC receive buffer overflow
352
Driver receive buffer overflow
801
Receive processing error
Link down error
Check the HUB or the link confirmation LED on the
communication unit. If the LED is not on, check
cable connection and the port setting on the network
table.
802
Transceiver error
Check the transceiver and cable connection.
900
No IP address at local port
Check that the IP address of the local port is set on
the network table.
Check if the same IP address is set on the network.
901
Duplicated IP address error
902
Send socket ID error (error that may
occur when V7i LAN port is used)
Turn the power off and back it on. If the problem
persists, contact your local distributor.
1000
Ethernet I/F unit not mounted
Check whether the Ethernet I/F unit is mounted
correctly, and then turn the power off and on.
If the problem persists, contact your local distributor.
1001
Ethernet I/F unit not ready
1002
Ethernet I/F unit DPRAM error
1003
No response from Ethernet I/F unit
1004
Ethernet receive buffer over
1005
Ethernet send registration error
1006
I/F unit unregistered interrupt
1100 to 1115
Initialization error (communication unit)
1120
Dual port access error
1200
Undefined register
1201
Send/receive buffer area over
1202
MAC address error
1203
Port error
Check whether the Ethernet I/F unit is mounted
correctly, and then turn the power off and on.
If the problem persists, contact your local distributor.
1301
Watch dog overflow
1302
JAVA error LANC error
Summary of Contents for V Series
Page 1: ...V Series...
Page 35: ...2 10 2 Allen Bradley PLC Please use this page freely...
Page 41: ...3 6 3 Automationdirect PLC Please use this page freely...
Page 49: ...6 4 6 FANUC PLC Please use this page freely...
Page 53: ...7 4 7 FATEK AUTOMATION PLC Please use this page freely...
Page 79: ...12 8 12 KEYENCE PLC Please use this page freely...
Page 95: ...14 8 14 LG PLC Please use this page freely...
Page 119: ...16 20 16 MITSUBISHI ELECTRIC PLC Please use this page freely...
Page 135: ...20 4 20 SAIA PLC Please use this page freely...
Page 155: ...24 12 24 Siemens PLC Please use this page freely...
Page 163: ...27 4 27 TOSHIBA PLC Please use this page freely...
Page 169: ...29 4 29 Toyoda Machine Works PLC Please use this page freely...
Page 185: ...33 6 33 Yokogawa Electric PLC Please use this page freely...
Page 215: ...App2 8 Appendix 2 n 1 Connection Multi link 2 Please use this page freely...
Page 221: ...App3 6 Appendix 3 n 1 Connection Multi link Please use this page freely...
Page 225: ...App4 4 Appendix 4 1 n Connection Multi drop Please use this page freely...
Page 317: ...App6 48 Appendix 6 Universal Serial Communications Please use this page freely...