Page 79
31-5000751 Rev. 0
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Code
Inverter Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Component or System Operational State and Troubleshooting
Tip
How to Clear Alert
Code
Red
LED
Green
LED
436
62
6
flashes
2
flashes
Service Soon/
Service
Urgent
OD Inverter
High Heat-Sink
Temperature
Inverter heat sink temperature exceeded limit.
•
This occurs when the heat sink temperature exceeds the inverter
limit. Inverter will issue inverter alert code 13 first and slow down to
try to cool the heat sink.
•
If temperature remains high, outdoor unit will stop both compressor
and fan – moderate condition.
•
Anti- short cycle is initiated.
•
If condition occurs five times within an hour, system will lockout –
critical condition.
•
The screws that hold the inverter to the inverter board were loose
causing poor contact between these two components.
•
Tighten screws that hold the heat sink to the inverter control board.
NOTE:
Wait five minutes for all capacitors to discharge before
checking screws.
•
Inverter LEDs will flash code 62.
•
Refer to the unit service documentation for detailed troubleshooting
procedures.
Inverter flash code 62.
The sequence is:
•
Red LED: Six Flashes
•
Green LED: Two Flashes
NOTE:
Inverter normal operations with no error code present is as
follows. Red LED is ON and Green LED is OFF.
Moderate condition
will automatically
clear when the
inverter sends an
alert code clear
message.
Critical condition
is cleared by
disconnecting power
to the outdoor unit
and restart.
437
65
6
flashes
5
flashes
Service Soon/
Service
Urgent
OD Inverter Heat-
Sink temp Sensor
Fault
Heat sink temperature sensor fault has occurred (temperature less
than 4ºF or greater than 264ºF after 10 minutes of operation).
•
When the temperature sensor detects a temperature less than 4ºF
or greater than 264ºF after 10 minutes of operation.
•
Outdoor unit will stop both compressor and fan – moderate
condition.
•
Anti-short cycle is initiated.
•
If condition occurs five times within an hour, system will lockout –
critical condition.
•
Inverter LEDs will flash code 65.
•
Refer to the unit service documentation for detailed troubleshooting
procedures.
Inverter flash code 65.
The sequence is:
•
Red LED: Six Flashes
•
Green LED: Five Flashes
NOTE:
Inverter normal operations with no error code present is as
follows. Red LED is ON and Green LED is OFF.
Moderate priority
condition will
automatically clear
when the inverter
sends an alert code
clear message.
Critical priority
condition can
be cleared by
disconnecting and
reconnecting power
to outdoor unit to
restart.
Table 24. Outdoor Control 7-Segment Display Alert Codes and Inverter LED Flash Codes