Page 75
31-5000751 Rev. 0
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Code
Inverter Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Component or System Operational State and Troubleshooting
Tip
How to Clear Alert
Code
Red
LED
Green
LED
430
26
2
flashes
6
flashes
Service Soon/
Service
Urgent
OD Inverter
Compressor
Startup Fail
Compressor start-up failure.
•
If condition is detected, outdoor unit will stop (compressor and fan)
– moderate condition.
•
Anti-short cycle is initiated.
•
If condition occurs 10 times within 60 consecutive minutes, the
system will lockout – critical condition.
•
Inverter LEDs will flash code 26.
•
Refer to the unit service documentation for detailed troubleshooting
procedures.
Inverter flash code 26.
The sequence is:
•
Red LED: Two Flashes
•
Green LED: Six Flashes
NOTE:
Inverter normal operations with no error code present is as
follows. Red LED is ON and Green LED is OFF.
•
Check refrigerant
•
Replace outdoor control board
•
Replace inverter.
To clear, disconnect
power to outdoor unit
and restart.
431
27
2
flashes
7
flashes
Service Soon/
Service
Urgent
OD Inverter PFC
Fault
The inverter has detected a PFC circuit over-current condition.
•
Error occurs when PFC detects an over current condition of 100A
peak.
•
If condition is detected, outdoor unit will stop (compressor and fan)
– moderate condition.
•
Anti-short cycle timer is initiated.
•
If condition occurs 10 times within 60 consecutive minutes, the
system will lockout – critical condition.
•
Inverter LEDs will flash code 27.
•
Refer to the unit service documentation for detailed troubleshooting
procedures.
Inverter flash code 27.
The sequence is:
•
Red LED: Two Flashes
•
Green LED: Seven Flashes
NOTE:
Inverter normal operations with no error code present is as
follows. Red LED is ON and Green LED is OFF.
To clear, disconnect
power to outdoor unit
and restart.
Table 24. Outdoor Control 7-Segment Display Alert Codes and Inverter LED Flash Codes