GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Code
Inverter Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Component or System Operational State and Troubleshooting Tip How to Clear Alert
Code
Red
LED
Green
LED
440
13
1 flash
3
flashes
Information
Only-Dealer
OD Inverter Com
-
pressor Slowdown
- High Heat-Sink
temperature
Compressor slowdown due to high heat sink temperature.
•
Heat sink temperature is approaching limit.
•
The compressor speed automatically slows to reduce heat sink
temperature.
•
The control sets indoor CFM and outdoor RPM to values according
to demand percentage rather than the actual Hz.
•
The screws that hold the inverter to the inverter board may be loose
causing poor contact between these two components.
•
Tighten screws that hold the heat sink to the inverter control board.
NOTE:
Wait five minutes for all capacitors to discharge before
checking screws.
•
This error code is primarily for informational purposes as the
inverter controls the compressor speed to operate within design
parameters. Typically the inverter will make a minor speed
reduction of 4 Hz (approximately a 5-6% speed reduction) for
a brief period of time and to reduce the heat sink temperature
and will then resume normal operation. This may occur at high
outdoor temperatures (above 110ºF) for brief periods of time (3 –
4 minutes) and is normal and expected operation of the inverter
controlling the compressor safely within design parameters.
•
The inverter finned aluminum heat sink is located on the back side
of the inverter in the condenser air stream. If the alert code 440
occur frequently, especially at lower outdoor temperatures, check
the heat sink for debris that may reduce heat transfer or possible
obstructions that may impact air flow across the heat sink.
•
The inverter will begin to briefly reduce the compressor speed when
the heat sink temperature rises above 185ºF and will allow the
inverter to resume the requested compressor demand speed once
the inverter heat sink reaches 176ºF. The heat sink temperature,
compressor speed in Hertz & the Inverter Compressor Speed
Reduction status (“On” or “Off ”) notification can be viewed under
the outdoor unit Diagnostics section of the thermostat dealer
control center.
•
Inverter LEDs will flash code 13.
•
Refer to the unit service documentation for detailed troubleshooting
procedures.
Inverter flash code 13.
The sequence is:
•
Red LED: One Flash
•
Green LED: Three Flashes
NOTE:
Inverter normal operations with no error code present is as
follows. Red LED is ON and green LED is OFF.
Automatically clears
when the condition
no longer exists.
Table 19. Outdoor Control 7-Segment Display Alert Codes - Compressor