Page 4
7)
Connect the Power Transformer
a)
Connect the supplied 24V, 40VA Power Transformer using the supplied Power Cable (P/N: 44A07-1).
b)
Plug the Power Transformer into a 120 VAC outlet.
- The “AC ON” LED (D25) should illuminate.
- Within one minute, the “STATUS” LED (D24) should begin blinking at a rate of 1 blink per second.
24 VAC 40 VA
MODEL RT-R2440SL/M
REVERE
OR EQUIVALENT
44A07-1
TRANSFORMER
CABLE (Supplied)
POWER TRANSFORMER
8)
Connect the Battery
Unplug the Power Transformer to shut down the controller. Connect the black battery wire to the – (negative) battery terminal of
the supplied battery. Connect the red battery wire to the + (positive) battery terminal. The controller should not start.
a)
Plug in the Power Transformer. The system should
start.
b)
Unplug the Power Transformer. The system should
continue to run on the battery (the “STATUS” LED will
continue to flash).
c)
Plug the Power Transformer back in and secure it to the
outlet.
RED WIRE TO +
BLACK WIRE TO -
OR EQUIVALENT
POWER CELL PC5-12
BATTERY
12V 5AH