10
Model
Chassis depth
Rack requirements
CR16005E-F/CR16
010E-F
Total depth: 706.5 mm (27.82 in)
•
81.5 mm (3.21 in) from the
mounting surface of the
mounting brackets to the front
end of the cable management
brackets
•
625 mm (24.61 in) from the
mounting surface of the
mounting brackets to the latch
on the power supply
•
A minimum depth of 0.8 m (2.62 ft)
•
A minimum of 84.5 mm (3.33 in) between
the front rack posts and the interior side
of the front door (including the door lock
and handle).
•
A minimum of 628 mm (24.72 in)
between the front rack posts and the
interior side of the rear door (including
the door lock and handle).
describes the depth of the CR16006-F, CR16010-F (one fan tray), CR16010-F (two fan
trays), and CR16014-F chassis.
describes the depth of the CR16010H-F, CR16010H-FA
,
CR16018-FA, and CR16018-F chassis. Figure 9 describes the depth of the CR16005E-F and
CR16010E-F chassis.
Figure 7 CR16014-F chassis depth
(1) Ejector levers of the switching fabric modules
(2) Cable management bracket
661 mm
(26.02 in)
95 mm
(3.74 in)
2
1
1