9
Model
Chassis depth
Rack requirements
mounting brackets to the
ejector levers of the switching
fabric modules
If the rack meets these requirements and has
a minimum depth of 0.8 m (2.62 ft), you can
mount the router in the rack. As a best
practice, use a rack with a minimum depth of
1.0 m (3.28 ft).
CR16010-F (two
fan trays)
Total depth: 759 mm (29.88 in)
•
78 mm (3.07 in) from the
mounting surface of the
mounting brackets to the front
end of the cable management
brackets
•
681 mm (26.81 in) from the
mounting surface of the
mounting brackets to the
ejector levers of the switching
fabric modules
•
A minimum of 81 mm (3.19 in) between
the front rack posts and the interior side
of the front door (including the door lock
and handle).
•
A minimum of 684 mm (26.93 in)
between the front rack posts and the
interior side of the rear door (including
the door lock and handle).
If the rack meets these requirements and has
a minimum depth of 0.8 m (2.62 ft), you can
mount the router in the rack. As a best
practice, use a rack with a minimum depth of
1.0 m (3.28 ft).
CR16014-F
Total depth: 756 mm (29.76 in)
•
95 mm (3.74 in) from the
mounting surface of the
mounting brackets to the front
end of the cable management
brackets
•
661 mm (26.02 in) from the
mounting surface of the
mounting brackets to the
ejector levers of the switching
fabric modules
•
A minimum of 98 mm (3.86 in) between
the front rack posts and the interior side
of the front door (including the door lock
and handle).
•
A minimum of 664 mm (26.14 in)
between the front rack posts and the
interior side of the rear door (including
the door lock and handle).
If the rack meets these requirements and has
a minimum depth of 0.8 m (2.62 ft), you can
mount the router in the rack. As a best
practice, use a rack with a minimum depth of
1.0 m (3.28 ft).
CR16010H-F/CR16
010H-FA
Total depth: 777 mm (30.59 in)
•
114 mm (4.49 in) from the
mounting surface of the
mounting brackets to the front
end of the cable management
brackets
•
663 mm (26.10 in) from the
mounting surface of the
mounting brackets to the
chassis rear handles
•
A minimum of 117 mm (4.61 in) between
the front rack posts and the interior side
of the front door (including the door lock
and handle).
•
A minimum of 666 mm (26.22 in)
between the front rack posts and the
interior side of the rear door (including
the door lock and handle).
If the rack meets these requirements and has
a minimum depth of 0.8 m (2.62 ft), you can
mount the router in the rack. As a best
practice, use a single-door rack with a
minimum depth of 1.0 m (3.28 ft).
CR16018-F/CR160
18-FA
Total depth: 777 mm (30.59 in)
•
114 mm (4.49 in) from the
mounting surface of the
mounting brackets to the front
end of the cable management
brackets
•
663 mm (26.10 in) from the
mounting surface of the
mounting brackets to the
chassis rear handles
•
A minimum of 117 mm (4.61 in) between
the front rack posts and the interior side
of the front door (including the door lock
and handle).
•
A minimum of 666 mm (26.22 in)
between the front rack posts and the
interior side of the rear door (including
the door lock and handle).
If the rack meets these requirements and has
a minimum depth of 0.8 m (2.62 ft), you can
mount the router in the rack. As a best
practice, use a single-door rack with a
minimum depth of 1.0 m (3.28 ft).
Summary of Contents for CR16000-F
Page 40: ...9 Figure 11 Securing the power cord method one Figure 12 Securing the power cord method two...
Page 47: ...16 Figure 22 Installing an SMB coaxial clock cable...
Page 66: ...5 Figure 5 Removing a common card Figure 6 Removing a card with a locking clip 1 3 2...
Page 76: ...15 Figure 19 Replacing an SMB coaxial clock cable...
Page 89: ...12 Figure 14 Example of a device label...