Windsor 500 Programming Manual - Issue C
- 71 -
Alarm comm menu
Paging
Windsor supports 2 different paging formats
21
. You can also program the pager type as part of
the telephone number programming.
1=ADEMCO
2=Stored Msg
If ADEMCO is programmed Windsor will report the subscriber ID, the ADEMCO event code
and the channel number to the pager. If stored message is programmed the channel number
in alarm is reported to the pager which should be programmed to display a text message for
each channel.
Alarm comm menu
Home Set
Windsor can be programmed to only trigger the alarm communicator device when the system
is set. If home set is on and all areas are not set then Windsor will not trigger the alarm
communicator device if a NA, 24Hr, ER or entry alarm occurs. Home set applies to all formats
and communicator types.
Home Set
Off
On/Off
Alarm comm menu
Verify Alm
Individual circuits on Windsor can be programmed to signal as verified alarms to a central
station (See Circuit Options/Verify Alm). Verified alarms can be signalled in ADEMCO fast,
point ID or Guardall formats.
Verify Alm
System
Help menu
Duration-000
000-255 minutes
Cct Alarm-Off
On/Off
Verify Alm menu
Areas
Windsor can be programmed to confirm alarms from any verified circuit in the system or only
confirm alarms from another circuit in the same area.
0=System
Confirm by any verified circuit in the system.
1=Areas
Confirm only by a verified circuit in the same area.
Verify Alm menu
Duration
The verified alarm duration is the maximum time between the first circuit to alarm and the
confirming circuit alarm. If a duration of 000 is programmed then the verification period will be
until unset.
Verify Alm menu
Cct Alarm
Windsor will, by default, only signal the confirmed alarm. If the Cct Alarm option is on Windsor
will transmit both the individual circuit alarms and the verified alarm.
21
Currently in the UK only Mercury pagers support Stored message format. Paging is not available in
the Windsor HS variant.