Operation
Power generation system operation
5.5.2
Power distribution and connection of devices
Danger
Danger to life through electric shock
y
Insulation monitors can mutually influence each other.
►
Do not connect any other insulation monitors downstream
of the power generation system.
Warning
Risk of damage
y
An overvoltage may arise when the pole-reversing switch is
switched on.
►
Before switching over the rotary field, you must switch the
optional pole-reversing switch to position “0”. Leave the
pole-reversing switch in position “0” until all connected
motors have come to a stop.
Important
Risk of damage
y
The total power draw of all connected units must not exceed
the output indicated for the current power generation system.
►
Only connect as many units as the generator output can
supply sufficiently.
►
Do not overload the generator.
Important
Risk of damage
y
Devices with deviating voltage and frequency may be
damaged upon connection.
►
Only connect devices which have voltage and frequency
data on their rating plate matching that for the power
generation system.