Installation of generator
Installation of generators of model 160
3.6
Installation of generators of model 160
y
To install the generators of model 160, proceed according to the
descriptions in this section.
y
Prior to installation, read the safety instructions in section 3.1 and sections
3.2 to 3.4 attentively and follow the instructions and information therein.
Caution
Risk of accident
y
Incorrectly attached lifting equipment can lead to accidents.
►
Secure the lifting equipment to the generator exclusively
using the ring screws provided.
►
Only use suitable lifting equipment.
3.6.1
Installation dimensions
and assembly
During assembly, observe the minimum
clearances and specifications for cooling in the
following section.
Dimensions, generator
ð
drawing sheet in the
Appendix.
y
Secure the generator with at least four
mounting screws (minimum M12 or
comparable, bolt grade min. 8.8).
y
The attachment must be permanent and
resistant to shock and vibrations.
y
Use suitable means to prevent the screws
from coming undone by themselves, e.g. via
a tension ring according to DIN 128.
y
Tightening torque for mounting screws: M = 87 Nm
y
Permissible load of the shaft: Fr
max
= 5,000 N (measured in 60 mm
axial clearance from the point where the shaft exits the bearing plate)
Fa
max
= 500 N
4 Mounting screws
Fr
max
Fa
max