GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 34
If the input code is beyond the available range or if the modification is unsuccessful, the
screen will remain unchanged and waits to be modified.
7.5.2 Sensitivity Modification
Selecting
“2.Sense Modify” in the screen of Fig. 7-6, the system will enter the screen in Fig.
7-11.
2.Code Sense
1.Zone Sense
Fig. 7-11
(1)
“Zone Sense” is used to modify the sensitivity of all detectors from a zone.
(2)
“Code Sense” is for a specific detector.
There are three sensitivity levels: 1. High (H) 2. Moderate (M) 3. Low (L)
Selecting
“1. Zone Sense” will enter the screen shown in Fig. 7-12.
Zone: Sense:
1.H 2.M 3.L
1
2
Fig. 7-12
Note: The sensitivity of all detectors of the selected zone will change after modification
here.
Selecting
“2.Code Sense” in the screen of Fig. 7-9 will enter the screen in Fig. 7-13.
Sense: H
Code: Zone:6
210
1
Fig. 7-13
Note: The device sensitivity will change after modification here.
7.6 Device Monitoring
Selecting
“5.Monitoring” in the screen of Fig. 7-1 will enter the screen of device monitoring. If
it is digital loop device, the screen will be as in Fig.7-14.
Code:
Digital
Value:[ 0204 ]
162
Fig. 7-14