GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 32
Repeated! Please
browse history!
Fig. 7-4
Disposal of duplicated codes:
(1) Press
History
and select
“”All History” option;
(2) The duplicated codes are shown as in Fig. 7-5, in which device No. 2 and 5 are
duplicated.
Doub-
le
001/020 1-002
15/12 13:26
Doub-
le
002/020 1-005
15/12 13:26
Fig. 7-5
(3) Modify the code to an unused number within 1
~
242 by handheld programmer. If
it
’s a digital device, the “Code Modify” option of the FACP can be used (refer to
Section 7.4.1).
(4) Press
System
and select
“2. Register” to re-register the device.
7.4 Password Setting
7.4.1 Classification of the passwords
Operation to functional keys except
View Fire
,
Tab
,
History
, and
Browse
requires password.
Only after the correct password is input, further operation can be done. For system security,
there are two levels of password, password I and password II.
Functions that can be performed by password I are User Setup, Disable/Enable, Self-test,
Reset, Evacuate and Silence. Password II is used for system settings.
Note: Password levels are downwards applicable (e.g. if a User enters the level 2
password, they have access at all levels).
7.4.2 Modification of the password
Selecting
“3.Password” in the screen of Fig. 7-1 will enter password setting screen as in Fig.
7-6.
2.Password II
1.Password I
Fig. 7-6