GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 23
The first screen
1.Zone
2.Devices
The second screen
3.Outputs
4.Pre-Alarm
The third screen
5.Output Delays
Fig. 6-8
Operations that can be disabled and enabled are:
⑴
Zone: Disabling/enabling all devices of a zone.
⑵
Devices: Disabling/enabling an individual device.
⑶
Outputs: Disabling/enabling a selected output so that it cannot be triggered.
⑷
Pre-Alarm: Disabling/enabling the pre-alarm mode of detectors.
⑸
Output Delays: Disabling/enabling output delay.
If there is a device in trouble or false alarm, you can disable it so that it
’s separated from
registered devices. After it
’s repaired or replaced, you can then enable it again and the FACP
will add it to registered devices.
6.5.1 Disabling / Enabling a Zone
In the screen of Fig. 6-8, selecting
“1. Zone”, the system will display zonal disable screen as in
Fig. 6-9.
Disabled Sum: 0
Disabled:Z- [ ]
1
Fig. 6-9
Input the zone number, and press
Enter
, all devices of the zone will be disabled and an
asterisk
“*” will appear in the “[ ]”. The zonal
Flt/Disabled
LED illuminates. The first line