GST100 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 31
Device Type:
Code: Zone:
1
025
03
Fig. 7-2
You can input the device code after
“Code”, and zone number after “Zone”, in which “0”
stands for the common zone, and then input the device type. The icon of the device type will
be displayed to avoid any possible mistake. Pressing
Enter
will complete the definition.
After a device is successfully defined, the following device code will automatically increase by
1, with other messages remaining unchanged. If the definition fails, the device code will
remain unchanged for re-definition.
Inputting the device code in monitor status, its definition message is automatically displayed
which can be modified by the user. Inputting the device code in commission status the initial
value of the device will be displayed.
7.3 Device Registration
Selecting
“2.Register” in the screen of Fig. 7-1 will enter the screen of device registration as
in Fig. 7-3.
[021] Sum: 014
Registering...
[ ] Sum: 015
Registering...
022
Fig. 7-3
The device code is displayed in the
“[ ]” during device Registration. If the device code is
highlighted, this means it is registered and the total number of registered devices increases. If
the device number is not highlighted, then the device is not registered. The system enters
normal monitoring state after registration.
We can see from Fig, 7-3, device No. 021 is not registered and the total number remains
unchanged. Device No. 022 is registered and the total number increased by 1.
The FACP is able to identify duplicated codes and write into running record for the user to
modify. If there are duplicated codes, the screen will display the following message after
registration (Fig. 7-4).