5.4.2 Disposal of Fire Message
When fire alarm occurs, first find out the location according to the information shown on the
FACP to verify if it
’s a real fire. If it’s real, you can take the following measures.
(1) Press
EVAC
key to warn people to evacuate.
(2) Organize specially trained personnel to try to control the fire.
(3) Call the fire brigade.
If it is false, please take the following measures.
(1) Press
Silence
to stop the sounders.
(2) Remove the factors that caused the false alarm. Press
Reset
to make the control
panel back to normal state.
(3) If the false alarm is caused by the malfunction of fire detection device, disable it and
inform the manufacturer for repair.
5.5 Fault Message
5.5.1 Fault Message Display
When fault occurs, the FACP will give fault signal in 100 seconds.
(1) The LCD displays the fault message as shown in Fig. 5-4.
(2) The speaker of the FACP gives fault sound
(
ambulance sound
)
. The common
Fault
LED illuminates.
If fault output is enabled, the normally open contact of FAULT OUTPUT contact (NO, COM) is
closed, and the normally closed contact is open.
The FACP will indicate differently for different type of fault message.
If a field device is in trouble, the zonal
Flt/Disable
LED flashes.
If the AC power is down, the FACP reports AC fault, the
AC Fault
LED illuminates.
If the battery voltage is lower than 18V, the
Battery Fault
LED illuminates.
If it
’s a fault with the memory, the
System Fault
LED illuminates. If the program
cannot be executed because of an internal fault or the damaged CPU, the
Fault
and
System Fault
LED illuminate intermittently, and the speaker gives tick-tick sound.
If one of the detectors report dirty, the LCD displays
“Dust” at the section of current