6.6.3 Delay Setup
Selecting
“3. Delay Setup” in the screen of Fig. 6-8 will enter delay setup screen shown in Fig.
6-19.
2.Common Delay
1.Zone Delay
Fig. 6-19
(1) Zone/STG 1: If pre-alarm is enabled, this is for setting the delay time of the first stage
of pre-alarm. If pre-alarm is disabled, this is for setting the output delay time for the
zonal sounders, which is maximum 600 seconds.
(2) Common/STG 2: If pre-alarm is enabled, this is for setting the delay time of the second
stage of pre-alarm. If pre-alarm is disabled, this is for setting the output delay time for
the common sounders or ALARM OUTPUT and SOUNDER OUTPUT (R+, R-), which
is maximum 600 seconds.
Selecting 1 or 2 in the screen of 6-19 will enter setting screen as in Fig .6-20.
Delay: S
200
Max Delay 600s
Fig. 6-20
6.6.4 Network Setup
Please refer to Chapter 8 for description of network setup.
6.7 Evacuate
If a fire alarm is acknowledged as a real fire, pressing
EVAC
key will immediately start all
sounders and SOUNDER OUTPUT (R+, R-) to warn people to evacuate. Pressing
EVAC
, the
system will request a password. Entering the correct password and pressing
Enter
will
enable the evacuate function.
6.8 Alarm Silence
If a fire occurs, the zonal and common sounders will be activated to give the alarm sound.
Pressing
Silence
can stop the sound (if the keypad is locked, Level 1 password is required),
and the
Silence
LED will illuminate. The second press on
Silence
key or a new-coming fire
alarm will re-start the sounders, and the
Silence
LED goes off.
6.9 Reset
The FACP shall be reset after a fire alarm or a fault is disposed. Reset can be done by pressing
Reset
key and inputting the password and pressing
Enter
.