English (GB)
73
Water flow too
low
FIAHL 0.02 flow rate min.
• Low water inlet pressure
• Contact the local authorities.
• Water inlet flow sensor (0.02)
damaged or polluted
• Clean or replace the sensor.
• Filter in pressure reducing
valve (V0.02) blocked
• Check and clean.
• Wrong setting
• Check and adjust the water flow. See section
7.2.4 Checking and adjusting the soft water
flow and the salinity of the electrolyte
Water flow too
high
FIAHL 0.02 flow rate max.
• Wrong setting
• Check and adjust the water flow. See section
7.2.4 Checking and adjusting the soft water
flow and the salinity of the electrolyte
• Water inlet flow sensor (0.02)
damaged or polluted
• Clean or replace the sensor.
Fault in
ventilation
FIAHL 4.13 flow rate min.
FIAHL 4.13 flow rate max.
Fan EF4.01 faulty
Fan EF4.02 faulty
• Exhaust air line (4) blocked or
broken
• Check and rectify.
• Power failure at fan
• Check the fuses.
• Motor failure at fan
• Replace the fan.
• Wrong setting
• Check and adjust the flow rate. See section
.
• Air flow sensor (4.13) wrongly
installed
• Check the hoses and connections of the flow
sensor. See section
venturi nozzle (VN) and flow sensor (4.13)
• Faulty connection of the
venturi nozzle (VN)
• Air flow sensor (4.13)
damaged
• Replace the sensor.
Degassing and
storage tank
filling level too
high
Tank level LIAHL 4.10 max.
• Failure of degassing tank level
sensor (4.10)
• Check and adjust. See section
7.1.3 Degassing and storage tank
• Solenoid valve (0.05) failure
• Check and clean the valve seat. Replace, if
the fault persists.
Degassing and
storage tank
filling level too
low
Tank level LIAHL 4.10 min.
• Selcoperm electrolyser
stopped (locally or remotely)
• Check and rectify.
• Sodium hypochlorite solution
demand too high
• Reduce the demand.
• Failure of degassing tank level
sensor (4.10)
• Check and adjust. See section
7.1.3 Degassing and storage tank
• Degassing and storage tank
(E4.05) leaking
• Check and rectify.
Electrolyte level
in cells too low
Cell level LSAL 1.09
Cell level LSAL 2.09
Cell level LSAL 3.09
• Electrolysis cell damaged
• Check and replace.
• Wrong adjustment
• Readjust the sensor. See section
7.2.5 Checking and adjusting cell outlet level
switches (1.09, 2.09, 3.09)
.
Wrong filling
level in NaClO
solution line
Pipe filling level LSAL 4.04
Pipe filling level LSAL 4.04 full
• Piping damaged
• Check and rectify.
• Wrong installation
• Check and rectify. See section
7.2.6 Checking and adjusting NaClO level
switch (4.04)
.
Leakage in
Selcoperm
electrolyser
Level switch electrolyser LSAH
0.01
• Solenoid valve (0.05) failure
• Check and clean the valve seat. Replace, if
the fault persists.
• Leakage in piping
• Check and rectify.
• Sample valve (V0.06, V0.09)
or acid valve (V0.07) open
• Check and rectify.
Fault
Display text
Possible cause
Possible remedy (certified service persons)