English (GB)
61
8.5.33
Settings alarm delays
In this menu, the alarm delay times can be viewed and changed.
Fig. 69
Settings alarm delays
Details on start and stop delays can be found in section
.
To change a value, touch the respective field and enter the new
value via the numeric keyboard. See section
To save the settings, push [
].
To reset the values to factory settings, push [
].
To revert to the previous menu, push [
].
For details on general menu symbols see section
.
8.5.34
Settings delay-/flushing times
Each time the system enters or leaves the operating state
"Production", the delay times in this menu are used for starting
and stopping the respective components.
Fig. 70
Settings delay-/flushing times
Details on start and stop delays can be found in section
To change a value, touch the respective field and enter the new
value via the numeric keyboard. See section
.
To save the settings, push [
].
To reset the values to factory settings, push [
].
To revert to the previous menu, push [
].
For details on general menu symbols see section
Menu action
Required user level
Access menu
3
Commissioning staff
Change settings
3
Commissioning staff
Reset to factory settings
3
Commissioning staff
ID 0
1
2
0
Display text
Description
Alarm
changeover
delay
Fault delay time settings for brine pumps and
degassing fans.
•
Brine pumps
Fault delay time settings for brine pumps.
•
Fan
Fault delay time settings for degassing fans.
Level cell line
LSAL x.09
Settings for level switches of cell lines (1.09,
2.09, 3.09). See section
.
•
Start delay
Each time the system is manually set from
operating state "Stop" to "Production" (locally
or remotely), this time period is allowed to
elapse before the level switches detect liquid.
If no liquid is detected within this time period, a
fault message is displayed.
Pipe filling
level LSAL
4.04
Settings for NaClO solution line level switch
(4.04). See section
.
•
Start delay
Each time the system is manually set from
operating state "Stop" to "Production" (locally
or remotely), this time period is allowed to
elapse before the level switch detects liquid. If
no liquid is detected within this time period, a
fault message is displayed.
•
Deactivate
Each time the system is manually or
automatically set to operating state "Standby"
or "Stop", this time period is allowed to elapse
before the level switch stops detecting liquid. If
liquid is detected after this time period, a fault
message is displayed.
Menu action
Required user level
Access menu
3
Commissioning staff
Change settings
3
Commissioning staff
Reset to factory settings
3
Commissioning staff
ID
0
1
21
Display text
Description
Fan
Settings for the degassing fan.
•
Start delay
Time period from starting the fan until the
solenoid valve is opened and the brine pump is
started.
•
Stop delay
Time period from stopping the brine pump until
the fan is stopped.
Electrolyte
Settings for the electrolyte flow.
•
Start delay
Time period from opening the solenoid valve
and starting the brine pump until the system
starts to analyse the level switches (1.09, 2.09,
3.09). See section
•
Stop delay
Time period from switching off the DC current
of the cells until the brine pump is stopped and
the solenoid valve is closed.