Installation
29 | 74
BA_
T
D
3-
BM
001e
n_
01
4_D
el
ta-
p.docx
Fill the resin and glass dry into the exchangers. Wet filling is only allowed immediately before
start-up. If this is not possible, the water softener must be disinfected before starting up
(refer to chapter
Fehler! Verweisquelle konnte nicht gefunden werden.
).
Delta-p
1½"
2"
Quantity of
glass
[l]
10
15
Quantity of resin
[l]
75
100
You may order spare parts and consumables from your local Grünbeck representative, refer
to the Internet at www.gruenbeck.de.
Proceed as follows to fill the exchangers:
1.
Unscrew the bottle adapter by turning it to the left.
2.
Centre the riser pipe in the exchanger.
3.
Put on the filling adapter.
4.
Place the pipe section on the filling adapter.
5.
Fill the glass through the funnel into the exchanger.
6.
Make sure that the glass filling is evenly distributed.
7.
Fill the resin through the funnel into the exchanger.
8.
Remove the funnel, pipe section and filling adapter.
9.
Clean the threads and sealing surfaces on the exchanger for the connection of the
bottle adapter to remove any glass and resin adhering to them.
10.
Place the bottle adapter from above with the head nozzle in front over the riser
pipe.
11.
Tighten the bottle adapter by turning it to the right.
» The exchanger is filled.
5.4.2
Installation
For the plug-and-play-installation instructions for the water softener Delta-p, refer to
chapter 13.
Summary of Contents for Delta-p
Page 1: ...We understand water Softening Water softener Delta p Operation manual ...
Page 57: ...Mounting instructions 57 74 BA_TD3 BM001en_014_Delta p docx ...
Page 58: ...Mounting instructions 58 74 BA_TD3 BM001en_014_Delta p docx ...
Page 59: ...Mounting instructions 59 74 BA_TD3 BM001en_014_Delta p docx ...
Page 60: ...Mounting instructions 60 74 BA_TD3 BM001en_014_Delta p docx ...
Page 62: ...Mounting instructions 62 74 BA_TD3 BM001en_014_Delta p docx ...
Page 72: ......