Cleaning, inspection, maintenance
39 | 74
BA_
T
D
3-
BM
001e
n_
01
4_D
el
ta-
p.docx
8.3
Inspection
WARNING:
Danger of contaminated drinking water if the work is not carried out properly.
● Risk of infectious diseases.
► Pay attention to hygiene when working on the installation.
● Determine the raw water hardness. To do this, use the water test kit "total
hardness".
● Determine the soft water hardness. To do this, use the water test kit "total
hardness".
● Check the amount of salt in the brine tank. When doing this, pay attention to the
minimum amount of salt in the brine tank and, if necessary, top up with salt tablets
according to DIN EN 973 A (refer to chapter 6.1.1)
● Check the system for leaks.
● Check the tightness of the control valve to the drain in the operating state, without
regeneration procedure.
8.4
Maintenance
8.4.1
Semi-annual maintenance
WARNING:
Danger of contaminated drinking water if the work is not carried out properly.
● Risk of infectious diseases.
► Pay attention to hygiene when working on the installation.
The following work must be carried out as part of the semi-annual maintenance:
● Read the water meter.
● Determine the raw water hardness. To do this, use the water test kit "total
hardness".
● Determine the soft water hardness. To do this, use the water test kit "total
hardness".
● Check the setting of the control unit:
• Time
• Actual raw water hardness
• Soft water hardness with blending.
Not allowed to be changed on Delta
-
p
-
I
.
Summary of Contents for Delta-p
Page 1: ...We understand water Softening Water softener Delta p Operation manual ...
Page 57: ...Mounting instructions 57 74 BA_TD3 BM001en_014_Delta p docx ...
Page 58: ...Mounting instructions 58 74 BA_TD3 BM001en_014_Delta p docx ...
Page 59: ...Mounting instructions 59 74 BA_TD3 BM001en_014_Delta p docx ...
Page 60: ...Mounting instructions 60 74 BA_TD3 BM001en_014_Delta p docx ...
Page 62: ...Mounting instructions 62 74 BA_TD3 BM001en_014_Delta p docx ...
Page 72: ......