Control unit
23 | 74
BA_
T
D
3-
BM
001e
n_
01
4_D
el
ta-
p.docx
4.5.2
Advanced programming menu level
Status level>Advanced programming menu level
Parameters of the Advanced programming menu level
Control unit GENO-IONO-matic
3
Index/parameters
Meaning
Factory
setting
Setting range
0
Programmable input
function
0 = No function
1 = External release of regeneration
2 = External lock of regeneration
3 = External 3-way regeneration
triggering
4 = Reserved function
0
0 ... 2
1
Programmable output
function
0 = No function
1 = Closed during regeneration step
1 Salting
2 = Closed during the entire
regeneration
3 = Closed if flow rate with flow at
exchanger * and
exchanger ** = 0 m³/h or with
bottle changeover or in case of
malfunction
80/210 = reserved function
0
0 ... 3/80/210
2
Delay time for
programmable output
with setting = 3
After the bottle changeover has been
completed, the contact opens again
with a delay.
͘0.5
0.1 … 9.9
3
Activation pre-alarm
salt supply (optional)
0 = is not evaluated
L = Infrared-light sensor detects the
filling level in the brine tank. If no
object is detected within the
adjustable switching gap for
longer than 5 min, warning Er A +
symbol
appears
0
0 ... 999/L
reserved function
0
1 … 999
4
Serial interface RS 485
0 = deactivated
1 = Optional module
DE2000 Profibus available
2 = Protocol mode RTU for
networking with reverse osmosis
GENO-OSMO-X
0
͘0 … 2
5
Pulse divider for
EXAcount pulse
output 1: …
The input pulses of the water meters
exchanger */exchanger **/blending
are used for the pulse output.
1
(0)/1/12/18/31/42
Note:
Divider "0" must not be used in
combination with the dosing
computer EXADOS!
Setting "0" is reserved for the
Delta-p- cascade circuit.
Observe the following tables.
Summary of Contents for Delta-p
Page 1: ...We understand water Softening Water softener Delta p Operation manual ...
Page 57: ...Mounting instructions 57 74 BA_TD3 BM001en_014_Delta p docx ...
Page 58: ...Mounting instructions 58 74 BA_TD3 BM001en_014_Delta p docx ...
Page 59: ...Mounting instructions 59 74 BA_TD3 BM001en_014_Delta p docx ...
Page 60: ...Mounting instructions 60 74 BA_TD3 BM001en_014_Delta p docx ...
Page 62: ...Mounting instructions 62 74 BA_TD3 BM001en_014_Delta p docx ...
Page 72: ......