Super Free Match
Service Manual
CONTROL
58
4
Smart Zone Controller (CE50-24/E)
4.1
General Introduction
4.1.1 Function Introduction
This smart zone controller is a kind of regional controller, which is designed for free match units, capable of
controlling up to
3 outdoor units and 16 indoor units
.
Through this smart zone controller, it is available to view and control those running parameters of the indoor
unit, including on/off, running mode, fan speed etc, and also perform the single control and centralized control,
further, it also can set the weekly timer and long-distance shielding to realize convenient control to the air
conditioning system.
a. Single control: it is intended to control the running parameters of a designated indoor unit individually.
b. Centralized control: it is intended to control the running parameters of all indoor units at the same time.
c. Shielding under single or centralized control: it is intended to shield the running parameter of the indoor
unit.
d. Weekly timer under single or centralized control: it is intended to set when to start/stop the unit through
long-distance control.
e. Clock: it is intended to set and display the weekday, hour and minute.
After the debugging to the controller is finished, it can check the on-line indoor units and display the
parameter setting of the current running mode, set temperature, fan speed, weekly timer, shielding function etc.
When some error occurs, the error symbol and the error code will be displayed to warn a quick maintenance.
This smart zone controller can be connected to the unit through the communication line without the need of
the communication module, which can extremely ease and simplify the installation.
4.1.2 Scope of application
The smart zone controller cannot be adapted to all kinds of indoor units and the wired remote controller must
be used in the indoor units. So the wall mounted and console types are beyond the scope of the smart zone
controller.
Summary of Contents for R410A
Page 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201306 CENTRAL AIR CONDITIONERS ...
Page 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT ...
Page 28: ...Super Free Match Service Manual CONTROL 24 CONTROL ...
Page 29: ...Super Free Match Service Manual CONTROL 25 Control 1 OPERATION FLOWCHART ...
Page 31: ...Super Free Match Service Manual CONTROL 27 1 2 Heating Operation ...
Page 66: ...Super Free Match Service Manual INSTALLATION 62 INSTALLATION ...
Page 97: ...Super Free Match Service Manual INSTALLATION 93 ...
Page 129: ...Super Free Match Service Manual MAINTENANCE N 125 MAINTENANCE ...
Page 153: ...Super Free Match Service Manual MAINTENANCE N 149 4 2 3 BU module FXB3A K ...
Page 154: ...Super Free Match Service Manual MAINTENANCE 150 FXB5A K ...
Page 217: ...JF00301896 ...