INSTALLATION
106
6.5
Design Requirements for Oil Trap
If the height different between the indoor unit and outdoor unit exceeds 6m, one oil trap shall be installed
every 6m from lower to upper on the vertical section of gas pipe. The oil trap shall be fabricated into two U-type
elbows or one return-type elbow. The height shall be 3~5 times the piping diameter.
See below for details on installation and fabrication of oil trap.
①
. The oil trap may be fabricated into U-type or return-type.
②.
If outdoor unit is below indoor unit, it is not needed to install oil trap on the vertical pipe of gas piping.
③
. If the outdoor unit is below the indoor unit, it is not needed to install oil trap at the highest or lowest
position. If the outdoor unit is above the indoor unit, oil trap and stop elbow must be installed at the lowest and
highest position of the vertical pipe. See the schematics below:
④
. Fabrication dimension of oil trap is as shown below:
⑤
. See the schematics below:
Outdoor unit lower than indoor unit
Summary of Contents for R410A
Page 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201306 CENTRAL AIR CONDITIONERS ...
Page 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT ...
Page 28: ...Super Free Match Service Manual CONTROL 24 CONTROL ...
Page 29: ...Super Free Match Service Manual CONTROL 25 Control 1 OPERATION FLOWCHART ...
Page 31: ...Super Free Match Service Manual CONTROL 27 1 2 Heating Operation ...
Page 66: ...Super Free Match Service Manual INSTALLATION 62 INSTALLATION ...
Page 97: ...Super Free Match Service Manual INSTALLATION 93 ...
Page 129: ...Super Free Match Service Manual MAINTENANCE N 125 MAINTENANCE ...
Page 153: ...Super Free Match Service Manual MAINTENANCE N 149 4 2 3 BU module FXB3A K ...
Page 154: ...Super Free Match Service Manual MAINTENANCE 150 FXB5A K ...
Page 217: ...JF00301896 ...