Super Free Match
Service Manual
PRODUCT
7
4
PRODUCT DATA
4.1
Product Data of Outdoor Unit
Model
Heat pump
GWHD(48S)NM3CO
GWHD(56S)NM3 CO
Cooling capacity
KW
14.0
16.0
Heating capacity
KW
16.0
18.0
Cooling
KW 4.40
5.0
Nominal input
Heating
KW 4.25
4.7
EER/COP 2.9/3.2
2.8/3.5
Maximum NO. of connectable indoor units
8 9
Min
50 50
Total capacity index of to be connected
indoor units
Max 135
135
Power supply
3Ph,380~415V,
50Hz
Dimensions (H
×
W
×
D)
mm
1345×900×340
1345×900×340
Net weight/Gross weight
kg
116/125
116/125
Sound pressure
level
cooling/heating
dB(A)
58
58
Type
Axial-flow
Fan
Air Flow Volume
m
3
/h 7000
7000
Name
R410A
Charge
kg 4.95
4.95
Refrigerant
Control
Electronic expansion valve
Type
FV50S
FV50S
Refrigerant oil
Charge
L 1.35
1.35
Type
Inverter
Rotary
Compressor
Quantity
1
Gas
mm
Φ
15.9
Φ
19.05
Piping
connections
Liquid
mm
Φ
9.52
Φ
9.52
System total
m
135
145
OU-BU m
55
total
BU-IN m
80
90
Piping length
1 room
BU-IN
m
15
OU-BU m
30
OU-IN m
30
Height
BU-BU
/
IN-IN
m 15
Cooling DB
℃
18~48
Operation range
Heating
℃
DB -10
~
24
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27
℃
DB, 19
℃
WB. Outdoor Temperature is 35
℃
DB. The rated heating capacity data is measured under the following
work condition: Indoor Temperature is 20
℃
DB. Outdoor Temperature is 7
℃
DB, 6
℃
WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
Summary of Contents for R410A
Page 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201306 CENTRAL AIR CONDITIONERS ...
Page 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT ...
Page 28: ...Super Free Match Service Manual CONTROL 24 CONTROL ...
Page 29: ...Super Free Match Service Manual CONTROL 25 Control 1 OPERATION FLOWCHART ...
Page 31: ...Super Free Match Service Manual CONTROL 27 1 2 Heating Operation ...
Page 66: ...Super Free Match Service Manual INSTALLATION 62 INSTALLATION ...
Page 97: ...Super Free Match Service Manual INSTALLATION 93 ...
Page 129: ...Super Free Match Service Manual MAINTENANCE N 125 MAINTENANCE ...
Page 153: ...Super Free Match Service Manual MAINTENANCE N 149 4 2 3 BU module FXB3A K ...
Page 154: ...Super Free Match Service Manual MAINTENANCE 150 FXB5A K ...
Page 217: ...JF00301896 ...