Super Free Match
Service Manual
MAINTENANCE
N
135
Service personnel shall collect the malfunction information as much as possible and research them
thoroughly, list these electrical parts which may cause malfunction, service personnel shall be able to determine
the specific reason and solve the faulted parts.
Observe the status of the complete device and do not observe the partial.
It is advised to start from the simple operation during analyzing, judging and confirming malfunction reason,
then conduct the complicated operations such removal of device, part replacement and refrigerant filling.
Find the malfunction reason carefully as unit may occur several malfunction at the same time and one
malfunction may develop into several malfunction, so entire system analysis shall be established to make the
judged result exact and credible.
3.1
Malfunction display: High Pressure Protection
3.2
Malfunction display: Low Pressure Protection
Summary of Contents for R410A
Page 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201306 CENTRAL AIR CONDITIONERS ...
Page 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT ...
Page 28: ...Super Free Match Service Manual CONTROL 24 CONTROL ...
Page 29: ...Super Free Match Service Manual CONTROL 25 Control 1 OPERATION FLOWCHART ...
Page 31: ...Super Free Match Service Manual CONTROL 27 1 2 Heating Operation ...
Page 66: ...Super Free Match Service Manual INSTALLATION 62 INSTALLATION ...
Page 97: ...Super Free Match Service Manual INSTALLATION 93 ...
Page 129: ...Super Free Match Service Manual MAINTENANCE N 125 MAINTENANCE ...
Page 153: ...Super Free Match Service Manual MAINTENANCE N 149 4 2 3 BU module FXB3A K ...
Page 154: ...Super Free Match Service Manual MAINTENANCE 150 FXB5A K ...
Page 217: ...JF00301896 ...