Gree GMV6 DC Inverter VRF Units Service Manual
6
Model
-
GMV-1175WM/G-X
GMV-1230WM/G-X
GMV-1295WM/G-X
GMV-1360WM/G-X
Heating power input
kW
13.1+16.9
16.9+16.9
16.9+20.1
20.1+20.1
Cooling current
input
A
24.7+29.0
29.0+29.0
29.0+36.6
36.6+36.6
Heating current
input
A
23.4+30.2
30.2+30.2
30.2+35.9
35.9+35.9
Rated power input
kW
26.85+27.41
27.41+27.41
27.41+27.41
27.41+27.41
Rated current
A
48+49
49+49
49+49
49+49
Cooling operation
range
°C
-5~52
-5~52
-5~52
-5~52
Heating operation
range
°C
-30~24
-30~24
-30~24
-30~24
Refrigerant type
-
R410A
R410A
R410A
R410A
Refrigerant charge
kg
8+8.3
8.3+8.3
8.3+8.3
8.3+8.3
Maximum drive IDU
NO.
unit
64
64
64
64
Gas pipe
mm
Φ38.1
Φ38.1
Φ38.1
Φ41.3
Liquid pipe
mm
Φ19.05
Φ19.05
Φ19.05
Φ19.05
Outline dimensions
(W × D × H)
mm
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690
Packing dimensions
(W × D × H)
mm
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855
Net weight
kg
350+350
350+350
350+355
355+355
Gross weight
kg
365+365
365+365
365+370
370+370
Model
-
GMV-1399WM/G-X
GMV-1455WM/G-X
GMV-1510WM/G-X
GMV-1565WM/G-X
HP
HP
50
52
54
56
Combination mode
-
12+18+20
10+20+22
10+22+22
12+22+22
-
GMV-335WM/G-X+
GMV-504WM/G-X+
GMV-560WM/G-X
GMV-280WM/G-X+
GMV-560WM/G-X+
GMV-615WM/G-X
GMV-280WM/G-X+
GMV-615WM/G-X+
GMV-615WM/G-X
GMV-335WM/G-X+
GMV-615WM/G-X+
GMV-615WM/G-X
Cooling capacity
kW
139.9
145.5
151.0
156.5
Heating capacity
kW
157.0
163.5
169.5
175.5
Outdoor static
pressure
Pa
0/110
0/110
0/110
0/110
Noise (sound
pressure level)
dB(A)
66
66
67
67
Power
-
380V-415V 3N~
50Hz/60Hz
380V-415V 3N~
50Hz/60Hz
380V-415V 3N~
50Hz/60Hz
380V-415V 3N~
50Hz/60Hz
Cooling power input
kW
7.7+12.3+13.8
6.2+13.8+16.2
6.2+16.2+16.2
7.7+16.2+16.2
Heating power input
kW
7.8+12.9+13.1
5.9+13.1+16.9
5.9+16.9+16.9
7.8+16.9+16.9
Cooling current
input
A
13.8+22.0+24.7
11.1+24.7+29.0
11.1+29.0+29.0
13.8+29.0+29.0
Heating current
input
A
13.9+23.1+23.4
10.5+23.4+30.2
10.5+30.2+30.2
13.9+30.2+30.2
Rated power input
kW
13.50+26.30+26.85
13.15+26.85+27.41
13.15+27.41+27.41
13.50+27.41+27.41
Rated current
A
24.1+47+48
23.5+48+49
23.5+49+49
24.1+49+49
Cooling operation
range
°C
-5~52
-5~52
-5~52
-5~52
Heating operation
range
°C
-30~24
-30~24
-30~24
-30~24
Refrigerant type
-
R410A
R410A
R410A
R410A
Refrigerant charge
kg
5.7+8+8
5.5+8+8.3
5.5+8.3+8.3
5.7+8.3+8.3
Maximum drive IDU
NO.
unit
66
69
71
74
Gas pipe
mm
Φ41.3
Φ41.3
Φ41.3
Φ41.3
Liquid pipe
mm
Φ19.05
Φ19.05
Φ19.05
Φ19.05
Outline dimensions
(W × D × H)
mm
930×775×1690+
1340×775×1690+
1340×775×1690
930×775×1690+
1340×775×1690+
1340×775×1690
930×775×1690+
1340×775×1690+
1340×775×1690
930×775×1690+
1340×775×1690+
1340×775×1690
Packing dimensions
(W × D × H)
mm
1000×830×1855+
1400×830×1855+
1400×830×1855
1000×830×1855+
1400×830×1855+
1400×830×1855
1000×830×1855+
1400×830×1855+
1400×830×1855
1000×830×1855+
1400×830×1855+
1400×830×1855
Net weight
kg
220+295+350
215+350+350
215+350+350
220+350+350
Summary of Contents for GMV6 Series