Gree GMV6 DC Inverter VRF Units Service Manual
10
Model
-
GMV-2525WM/G-X
GMV-2590WM/G-X
GMV-2655WM/G-X
GMV-2720WM/G-X
Cooling current
input
A
29.0+29.0+29.0+
36.6
29.0+29.0+36.6+
36.6
29.0+36.6+36.6+
36.6
36.6+36.6+36.6+36.6
Heating current
input
A
30.2+30.2+30.2+
35.9
30.2+30.2+35.9+
35.9
30.2+35.9+35.9+
35.9
35.9+35.9+35.9+
35.9
Rated power input
kW
27.41+27.41+27.41+
27.41
27.41+27.41+27.41+
27.41
27.41+27.41+27.41
+27.41
27.41+27.41+27.41+2
7.41
Rated current
A
49+49+49+
49
49+49+49+
49
49+49+49+
49
49+49+49+
49
Cooling operation
range
°C
-5~52
-5~52
-5~52
-5~52
Heating operation
range
°C
-30~24
-30~24
-30~24
-30~24
Refrigerant type
-
R410A
R410A
R410A
R410A
Refrigerant charge
kg
8.3+8.3+8.3+8.3
8.3+8.3+8.3+8.3
8.3+8.3+8.3+8.3
8.3+8.3+8.3+8.3
Maximum drive IDU
NO.
unit
80(85)*
80(90)*
80(95)*
80(100)*
Gas pipe
mm
Φ44.5
Φ44.5
Φ44.5
Φ44.5
Liquid pipe
mm
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Outline dimensions
(W x D x H)
mm
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
Packing dimensions
(W x D x H)
mm
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
Net weight
kg
350+350+350+355
350+350+355+355
350+355+355+355
355+355+355+355
Gross weight
kg
365+365+365+370
365+365+370+370
365+370+370+370
370+370+370+370
Note:
*The maximum connection quantity of indoor unit in the brace should be engineering customized.
3
The Range of Production Working Temperature
—
Cooling
Heating
Ambient temperature
-5°C ~52°C DB
-30°C ~24°C DB
Indoor temperature
14°C ~25°C WB
15°C ~27°C DB
Indoor humidity
≤80%
When the indoor units are all VRF fresh air processor, the unit operating range is as follows:
Cooling
Ambient temperature: 16°C ~45°C
Heating
Ambient temperature: -7°C ~16°C
NOTE!
If exceeding the temperature range for working, the product may be damaged, which is not within
the warranty range.
Summary of Contents for GMV6 Series
Page 305: ...JF00304129 ...