"C4" Indoor Unit Loss Fault
Whether all the indoor
units are energized?
Power on the units
No
Connect the communication
cables properly
The main control board of the
indoor unit may be abnormal
Yes
Replace the main control
board
Yes
Whether the
communication cables of
disconnected indoor units
(in this case the disconnected
indoor units display "C0") are
connected properly?
2.31 "C5" Indoor Unit Engineering SN Conflict
Fault display:
commissioning software and remote monitoring software display the fault
;
The wired controller of indoor unit and receiver of indoor unit do not display the fault.
Fault diagnosis:
Check the engineering SN of indoor units, as the indoor units having the same numbers generate
the same fault. However, the fault is displayed and required to be removed only when the commissioning
software, centralized controller and remote monitoring are connected.
In the case of non-centralized control, the conflict in terms of the engineering SNs of some indoor
units, if any, do not affect the operation of themselves and of the entire system.
Possible causes:
■ The same engineering SN is configured for different indoor units;
■ The main board of indoor unit is from another unit.
Troubleshooting:
There are several ways to reset the conflicting engineering SN of an indoor unit:
by commissioning software;
by wired controller;
by commissioning the remote controller;
by pressing the Reset button on the main board of indoor unit so that the system reassigns the
numbers.
2.32 "C6" Alarm on Inconsistent Number of Outdoor Units
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit