NOTE!
When the compressor is working at another frequency, the current curve can be obtained through
interpolation calculation of the above frequency.
Step 2:
Check whether the running sound of the compressor is normal and whether any high-pitched sound
or obvious scratch can be heard. If there is a nearby unit running properly, compare the sound of the
compressor under inspection with that of the normally running unit.
Step 3:
Check whether the electronic expansion valve of the ODU and 4-way valve work properly, and
whether the oil-return pipeline and oil-return valve are normal. Touch the oil-return capillary tube with a
hand to check whether oil flows in the tube and check the pipeline temperature.
Diagnosis method:
1) Electronic expansion valve: When the unit is powered on and off each time, the electronic
expansion valve needs to reset. Touch the valve with a hand to check if the valve core rotates.
In the second half of the resetting process, the valve core will click and vibrate obviously.