Gree GMV6 DC Inverter VRF Units Service Manual
165
"P3" Reset Protection for
the Compressor Drive
Module
Is the problem solved after
the unit is powered off and powered on
for more than three times?
The compressor drive board
operates improperly
No
Replace the compressor drive
board
Yes
2.129 "P5" Inverter Compressor Over-current Protection
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is P5, it
indicates the over-current protection for the inverter compressor.
Possible causes:
■ Poor contact of compressor's UVW cables;
■ The compressor's UVW cables are wrongly connected;
■ The compressor
is damaged;
■ The system is blocked;
■ IPM module of the compressor drive board is damaged.
Troubleshooting: