Gree GMV6 DC Inverter VRF Units Service Manual
142
"J1" Compressor 1
Over-current Protection
The compressor is
abnormal
Yes
Yes
Replace the compressor
No
Replace the drive module
If the high pressure value
of the unit is still above 60°C when the compressor
runs at the lowest frequency, the compressor may
have enabled normal over-current protection. In this case, check
whether the fan operates properly and whether the ambient
temperature is normal and whether the power supply
is normal (320V-460V)
Power on again
the units based on the capacity
and number of indoor units enabled
previously in the case of
protection state
Whether the drive module is normal?
Yes
Yes
Is the protection still occurring
after power-on?
Yes