2.105 "L4" Supply Power Over-current Protection
Fault display:
wired controller of indoor unit and receiver of indoor unit display
Applicable models:
all indoor units
Fault diagnosis:
When the current supplied to the wired controller by the indoor unit is too large, the fault is generated.
Possible causes:
■ The wires of the wired controller are short circuited;
■ The main board of indoor unit operates improperly;
■ The main board of the wired controller is abnormal.
Troubleshooting:
"L4" Supply Power
Over-current Protection
Whether the power
cord of the wired controller is
short circuited?
Replace the wired controller
Yes
No
Reconnect the power cord of
the wired controller
Yes
No
Is the main board of the wired
controller abnormal?
The main board of indoor
unit operates improperly
Replace the main board of
indoor unit
Yes